Appendix C. Vendor Information

Appendix C.1. Installing SlotServer on a Remote Rack using CNB Cards

1

Appendix C.1.1.

Hardware and Software requirements

Two 1756 racks, one containing the CPU and the other the SlotServer

Two Controlnet CNB cards with connection cables to connect the racks to one other

RSlinx

RSLogix

RSNetworx

SlotServer EDS file (Available on SlotServer CD, or call Technical Support)

Appendix C.1.2.

Setup

Install the CPU and the first CNB card in the local rack.

Install the second CNB card and the SlotServer in the remote rack.

Connect the ControlNet Network

Power up the racks

Install the SlotServer EDS File using the RSLinx Hardware EDS Installation Tool.

Make sure the SlotServer has a valid configuration loaded. The default configuration shipped with the
SlotServer should suffice.

Refer to the SlotServer Configuration Manual for further information.

Note: When configured in remote rack applications, the SlotServer does not support the use of EN2T-A cards, but
is compatible with EN2T-B cards.

1

The principles for connecting other 1756 bridging cards to the SlotServer are similar.