Appendix a. useful features, Appendix a.1. led functions – FieldServer FS-RA-CLX-PRO User Manual

Page 8

Advertising
background image

SlotServer Start-Up Guide

Page 8 of 12

ProSoft Technology, Inc. is the exclusive provider of FieldServer SlotServers.

For Technical Support call +1 661.716.5100

Appendix A. Useful Features

Refer to the Configuration Manual for useful configuration features.

The unit may be removed under power for convenient swapping of modules.

Appendix A.1. LED Functions

Run

Node Off

Sys Err

LonSvc

Conf Err

Com Err

Rx

Tx

Service Pin

Figure 3: Diagram of SlotServer showing ports and displays

LED

Description

Run

When the SlotServer is powered up, this light will start flashing after approximately 2
minutes. If this light does not flash, it is an indication that the firmware is not
running, and that the SlotServer will not be operating.

LonSvc

This LED indicates LonWorks activity. Refer to Figure 3.

NodeOff

This light indicates that a device bound to the SlotServer on the LonWorks network is
not communicating. Use the LonWorks Network Manager to troubleshoot the
problem.

Conf Err

This light indicates an error in the configuration of the card. Since this model is
shipped pre-configured, this light should never come on unless the card
configuration is tampered with

Sys Err

This light indicates that an unexpected operation state occurred. The light can be
reset by cycling power to the card. If the error re-occurs persistently, then contact
FieldServer Technical support for assistance with troubleshooting after setting up
the trade port as shown in Appendix A.

Com Err

This light indicates that a communication error occurred. Use the LonWorks Network
Manager to troubleshoot the problem, or refer to the SlotServer configuration
Manual.

RS-485
(R1)

These lights are related to the RS-485 serial ports provided on the SlotServer. The Rx
(Receive) light will flash red if the FieldServer is receiving data. The Tx (Transmit)
light will flash red if the FieldServer is sending data. (Note that due to the nature of
2-wire RS-485 the Rx light will flash every time the Tx light flashes too). The
frequency of the flashing is directly related to the frequency of data transfer.

Ethernet Lights

These lights are related to the Ethernet network ports provided on the SlotServer.
The 10/100 light will be green if the physical connection to the network hub is
running at 100 MBits/s. If the light is off, the connection is running at 10 MBits/s.
The Act (Activity) light will indicate activity on the network. The frequency of
flashing is directly related to the network activity. It does not necessarily mean data
is being received by the FieldServer.

10/100

Act

The LonWorks Service pin can be used for commissioning the
SlotServer into a LonWorks network.

LonWorks Activity can be determined using this LED as follows:
LON LED Activity
Explicit Implicit

Not

Commissioned

Implicit

Commissioned

Off

Flashing

Off

Advertising