Venting installation – FMI COMFORT FLAME B42LI-M User Manual

Page 11

Advertising
background image

www.fmiproducts.com

115386-01D

11

Nail Only
Outer
Perimeter
of Flashing

Storm Collar

Underlap Shingles
at Bottom

Overlap
Shingles Top
and Sides Only

Figure 15 - Flashing Installation

Figure 16 - Storm Collar

Chimney
Pipe

Waterproof
Caulk

Storm
Collar

Flashing

Storm Collar Installation (SC1 or SC2)
Place storm collar over pipe and slide down
until it is snug against open edge of flashing
(see Figure 16). Use SC1 for all round ter-
minations and SC2 for all terminations with
slip sections. Apply waterproof caulk around
perimeter of collar to provide a proper seal.

Terminations/Spark Arrestor
Fireplace system must be terminated with
listed round top or chase terminations. In any
case, refer to installation instructions supplied
with termination. Terminations approved for
this fireplace are RT-8DM and RTL-8DM that
can be used for flashing or chase and ET-
8DM, ETO-8DM, ETL-8DM and ETLO-8DM
for chase style termination only. Figure 17
shows an RTL-8DM round top termination.

CAUTION: Do not seal open-

ings on the rooftop flashing. Fol-

low the installation instructions

provided with the termination

being used.

Flashing
Cone

VenTing inSTallaTion

Continued

Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws

RTL-8DM

Level of Flue
Gas Outlet

Caulk

Collar

Flashing

Underlap Shingles
Bottom Only

Figure 17 - Termination

Overlap
Shingles Top
and Sides

Terminations with 16" slip pipe sections are
available. RTT-8DM and RTTL-8DM are
approved for flashing installations. When
needed, these adjustable terminations may
be used in combination with pipe assembly
to achieve correct chimney height.
Note: In the rare instance there is a problem
with side driven rain or wind or chimney is
not drafting properly, an ADS-8DM (Anti-Draft
Shield) can be used with round terminations.

Flue Pipe of
RTL-8DM
Inside Inner
Pipe of
Chimney

CHASE INSTALLATIONS

Instructions for chase installations are includ-
ed with chase style termination chosen. In a
multiple chase installation, be sure to provide
adequate distance between terminations to
prevent smoke spillage from one termination
to another. We suggest that terminations be
separated at least 24", center to center and
stacked at a vertical height difference of 18"
(see Figure 18).
Note: If a decorative shroud is to be installed,
contact manufacturer for specification
s.

18" MIN. TYP

.

24" MIN.

24" MIN.

Figure 18 - Multiple Chase Installation