HEARTH ExTENSION

A hearth extension projecting a minimum of
20" in front of and a minimum of 12" beyond
each side of fireplace opening is required to
protect combustible floor construction in front
of fireplace. Fabricate a hearth extension
using a material which meets the following
specifications: a layer of noncombustible,
inorganic material having a thermal conductiv-
ity of K=0.84 BTU IN/FT, HR. F (or less) at 1"
thick. For example, if material selected has
a K factor of 0.25, such as glass fiber, the
following formula would apply:

0.25 x 1.0" = 0.30" thickness required

0.84

Thermal conductivity "K" of materials can be
obtained from manufacturer or supplier of
noncombustible material. If hearth extension
is to be covered, use noncombustible mate-
rial such as tile, slate, brick, concrete, metal,
glass, marble, stone, etc. Provide a means
to prevent hearth extension from shifting and
seal gap between fireplace frame and hearth
extension with a noncombustible material
(see Figure 3).

WARNING: Hearth extension

is to be installed only as shown

in Figure 3.

Fireplace inSTallaTion

Continued

Figure 3 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front
Raised Hearth

Fireplace Front
Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth

Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front
Elevated

Do Not Block Louver

Ember Protector

Seal Gap

Hearth

Extension

Hearth Extension, Circulating Modes

Hearth Extension, Noncirculating Models