Configuring the fieldserver as a bacnet ip server, Driver specific fieldserver parameters – FieldServer FS-8704-06 User Manual

Page 13

Advertising
background image

FS-8704-06 BACnet IP Driver Manual

Page 13 of 57

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

6

CONFIGURING THE FIELDSERVER AS A BACNET IP SERVER

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a BACnet/IP Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for BACnet/IP communications, the driver independent FieldServer buffers need to be declared in
the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section,
and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section.
Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

6.1

Driver Specific FieldServer Parameters

Section Title
Bridge
Column Title

Function

Legal Values

Title

FieldServer name

Text

Network_Number*

Specify a unique network number if there are multiple virtual Server
Nodes. Refer to Appendix A.2

1 – 65535, 5


Example

// FieldServer Driver specific parameters

Bridge

Title

BACnet Server