FieldServer FS-8704-06 User Manual
Page 24

FS-8704-06 BACnet IP Driver Manual
Page 24 of 57
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
FieldServer # 1
// Common Information
Bridge
Title
, System_Address
Server-1 Pumping Package #1 , 1
// Data Arrays
Data_Arrays
Data_Array_Name , Data_Format , Data_Array_Length
DA_AI
, UINT16
, 200
DA_AO
, UINT16
, 200
DA_DI
, Bit
, 200
DA_DO
, Bit
, 200
Connections
Adapter
, Protocol
, Connection_Type , IP_Port
N1
, Bacnet_IP , BBMD
, 47808
Nodes
Node_Name , Node_ID , Protocol
Server-1
, 11275
, Bacnet_IP
// Server Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
, Function
, Node_Name
, Object_Type
, Object_Instance
, Units
, Relinquish_Default
SCHWRemoteCall
, DA_DO
, 0
, Passive
, Server-1
, BO
, 1
, No-Units
, 0
SCHWCommonAlarm
, DA_DI
, 0
, Passive
, Server-1
, Bl
, 1
, No-Units , -