FieldServer FS-8704-06 User Manual
Page 23

FS-8704-06 BACnet IP Driver Manual
Page 23 of 57
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
The following diagram shows the layout of the connections between the FieldServers and the PC via a router.
BBMD Block Diagram
FS1
192.168.0.49
255.255.255.0
192.168.0.50
Node=11275
IP
Mask
GW
Router
192.168.0.50
255.255.255.0
0.0.0.0
IP
Mask
GW
PC
192.168.1.111
255.255.255.0
192.168.1.1
IP
Mask
GW
FS2
192.168.1.84
255.255.255.0
192.168.1.1
Node=11276
IP
Mask
GW
Mask
IP
255.255.255.0
192.68.1.1
// Bdt.ini
// The format of this table must be :
//
// BBMD IP_Address , BBMD port , BBMD subnet Mask
192.168.1.84
, 47808
, 255.255.255.255
192.168.0.49
, 47808
, 255.255.255.255
Configuration of the FieldServers is shown in the following examples.