Frymaster FOOTPRINT 8195991 User Manual

Page 14

Advertising
background image

2-5

Non-CE Standard

for Incoming Gas Pressures

Gas

Minimum

Maximum

Natural

6" W.C.

1.49 kPa

14.93 mbar

14" W.C.
3.48 kPa

34.84 mbar

LP

11" W.C.
2.74 kPa

27.37 mbar

14" W.C.
3.48 kPa

34.84 mbar

7. For fryers equipped with a FootPrint Pro system or basket lifts, plug the electrical cord(s) into a

power receptacle behind the fryer.

2.4

Connection to Gas Line

DANGER

Before connecting new pipe to this appliance, the pipe must be blown out thor-
oughly to remove all foreign material. Foreign material in the burner and gas con-
trols will cause improper and dangerous operation.

DANGER

When pressure-testing incoming gas supply lines, disconnect the fryer from the gas
line if the test pressure will be ½ PSIG (3.45 kPa, 13.84 inches W.C.) or greater to
avoid damage to the fryer’s gas tubes and gas valve(s).

DANGER

All connections must be sealed with a joint compound suitable for the gas being
used and all connections must be tested with a solution of soapy water before light-
ing any pilots.

Never use matches, candles, or any other ignition source to check for leaks. If gas
odors are detected, shut off the gas supply to the appliance at the main shut-off
valve and immediately contact the local gas company or an authorized service
agency for service.

DANGER

“Dry-firing” your unit will cause damage to the frypot and can cause a fire. Always
ensure that melted shortening, cooking oil, or water is in the frypot before firing the
unit.


The size of the gas line used for installation is very important. If the line is too small, the gas
pressure at the burner manifold will be low. This may cause slow recovery and delayed ignition.
The incoming gas supply line should be a minimum of 1½” (38 mm) in diameter. Refer to the chart
on the following page for the minimum sizes of connection piping.

Advertising