ELECTRONIC CONTROLS

IMPORTANT: Error Codes are cleared from the
log by exiting from Error Code Mode. To exit on XQ
models, press Timer On/Off button. To exit QME
models, press A/C Start and On/Off buttons. Or
unplug unit to exit Error Code Mode. Plug unit in after
5 seconds to resume normal operation of unit.

TESTING THE ELECTRONIC CONTROL

ERROR CODE LISTINGS

E1 SHORT CYCLE SITUATION: Keyboard is fine.
Investigate and defi ne short cycling problem.

E2 KEYBOARD STUCK ERROR: If key button(s) are
pressed continuously for twenty seconds or more. If MODE
key is stuck, unit will default to cool. Exit Error Code Mode to
see if error “E2” is no longer displayed and unit is functioning.
Replace board if “E2” still displays after exiting Error Code
Mode.

E3 FROST PROBE OPEN: If ohm value is present, replace
board.

E4 FROST PROBE SHORT: Replace board.

E5 INDOOR PROBE OPEN: Replace board.

E6 INDOOR PROBE SHORT: Replace board.

NOTE: All Error Code displays for Frost & Indoor Probe will allow
unit to operate. Unit may or will ice up if faulty components not
replaced.

FROST PROBE SENSOR: disables compressor at 35° F.

INDOOR PROBE SENSOR: Control range is 60° F to 90°
F +/- 2° F.

Indoor temperature will be displayed by pressing:

(QME units) The Fan Speed button and the Warmer button.

(XQ units) The Fan Speed button and the Temp Up button.

The indoor temperature will be displayed for 10 seconds.
The display will change back to the Set Point temperature

by pressing any key button except for the On/Off button. The
indoor temperature can be viewed in all modes, including
test mode.

Check Filter: The Check Filter indicator turns on after the

fan motor has been operating for 250 hours. The Check
Filter
indicator is reset by pressing the Check Filter button
one time only,. Power failures will not reset the 250 hour timer.

All time elapsed is stored in memory and resumes counting

after power is restored.

Keep Alive: The electronic control has a memory to retain
all functions and status as set up by the user in the event of
a power failure. Once power is restored to the unit there is a
two second delay before the fan comes on and approximately
three minutes delay before the compressor is activated,
providing that the mode was set for cooling and the set point
temperature has not been met in the room.

TESTING THE ELECTRONIC CONTROL

XQ/WS BOARDS & QME BOARDS

Activating Test Mode: Activate test mode by pressing at

the same time the “MODE” button and the temperature

“DOWN” button on XQ & WS models. LEDs for Hour, Start,

and Stop will blink 1 bps while Test Mode is active.

Activate test mode by pressing at the same time the “MONEY

SAVER” button and the “CHECK FILTER” button on QME

models. LED for the Filter Alert will blink 1 bps while Test
Mode is active.

Test Mode has duration of 90 minutes. Test Mode can be

activated under any conditions, including Off. Test Mode is
cancelled by pressing the On/Off button, unplugging the unit,
or when the 90 minutes is timed out. All settings revert to the
factory default settings of Cool, 75° F, Timer and Set Hour
features are nonfunctional.

Test Mode overrides the three-minute lockout, all delays for

compressor and fan motor start / speed change, and no
delay when switching modes.

Test Mode default settings are ON, Money Saver, 60° F, and

High fan speed.

Activating Error Code Mode: (Submode of Test Mode) Unit

must be in Test Mode to enter Error Code Mode

Activate Error Code Mode by pressing the “TIMER ON/OFF”

button on XQ & WS models. LED for the “TIMER ON/OFF”
will fl ash 1 bps while Error Code Mode is active. Pressing the

“TEMP/HR + “ button will display 00. Consecutive presses

will scroll through all error codes logged. Press the “TEMP/
HR - “
button to see the reverse order of all error codes
logged. When the end of logged error codes is reached the
temperature set point will appear.

Activate Error Code Mode by pressing at the same time the

“A/C START” button and the “ON/OFF” button on QME models.

LED for the “TIMER ON/OFF” will fl ash 1 bps while Error Code
Mode is active. Pressing the “WARMER” button will display 00.

Consecutive presses will scroll through all error codes logged.

Press the “COOLER” button to see the reverse order of all error
codes logged. When the end of logged error codes is reached
the temperature set point will appear.

TESTING THE ELECTRONIC CONTROL

ERROR CODE LISTINGS