Troubleshooting chart — cooling – Friedrich 2007 User Manual

Page 22

Advertising
background image

22

Problem

Possible Cause

Action

Unit cools when

heat is called for

Incorrect wiring

Refer to applicable wiring diagram

Defective solenoid coil

Check for continuity of coil

Reversing valve fails to shift

Block condenser coil & switch unit to cooling.
Allow pressure to build up in system, then
switch to heating. If valve fails to shift, replace
valve.

Inoperative system switch

Check for continuity of system switch

Problem

Possible Cause

Action

Cooling adequate,

but heating

insuffi cient

Heating capillary tube partially restricted

Check for partially starved outer coil. Replace
heating capillary tube

Check valve leaking internally

Switch unit several times from heating to
cooling. Check temperature rise across
coil. Refer to specifi cation sheet for correct
temperature rise

Reversing valve failing to shift completely;
bypassing hot gas

De-energize solenoid coil, raise head
pressure, energize solenoid to break loose.
If valve fails to make complete shift, replace
valve.

TROUBLESHOOTING CHART — COOLING

Low Suction Pressure

High Suction Pressure

Low Head Pressure

High Head Pressure

Low Load Conditions

High Load Conditions

Low Load Conditions

High Load Conditions

Low Air Flow Across

High Air Flow Across

Refrigerant System

Low Air Flow Across

Indoor Coil

Indoor Coil

Restriction

Outdoor Coil

Refrigerant System

Reversing Valve not

Reversing Valve not

Overcharged

Restriction

Fully Seated

Fully Seated

Undercharged

Overcharged

Undercharged

Noncondensables (air)

in System

Moisture in System

Defective Compressor

Defective Compressor

REFRIGERANT SYSTEM DIAGNOSIS – HEATING

HEAT / COOL ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS