Air for combustion and ventilation – FMI SVYD18NRA User Manual

Page 6

Advertising
background image

www.fmiproducts.com

113084-01L

6

Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of un-
usually tight construction, you must provide
additional fresh air.
Unusually tight construction is defined as
construction where:
a. walls and ceilings exposed to the out-

side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10

-11

kg per pa-sec-m

2

) or

less with openings gasketed or sealed
and

b. weather stripping has been added on

openable windows and doors and

c. caulking or sealants are applied to

areas such as joints around window
and door frames, between sole plates
and floors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.

If your home meets all of these three criteria,
you must provide additional fresh air. See
Ventilation Air From Outdoors, page 7.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-
Air Flow For Fireplace Location
.

Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/
NFPA 54
defines a confined space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m

3

per kw) of the aggregate

input rating of all appliances installed in that
space and an unconfined space as a space
whose volume is not less than 50 cubic feet
per 1,000 Btu/hr (4.8 m

3

per kw) of the ag-

gregate input rating of all appliances installed
in that space. Rooms communicating directly
with the space in which the appliances are
installed*, through openings not furnished
with doors, are considered a part of the un-
confined space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION

Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have
a confined or unconfined space.

Space: Includes the room in which you will install
fireplace plus any adjoining rooms with door-
less passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length

x width x height).

Length x Width x Height =__________cu. ft.
(volume of space)

Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)

If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can sup-
port.

________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free fireplace

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances* + _________ Btu/Hr

Total

= _________ Btu/Hr

* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.

Example:

Gas water heater

__________ Btu/Hr

Vent-free fireplace

+ _________ Btu/Hr

Total

= _________ Btu/Hr

4. Compare the maximum Btu/Hr the space

can support with the actual amount of Btu/
Hr used.

_______ Btu/Hr (maximum the space can
support)

_______ Btu/Hr (actual amount of Btu/Hr
used)

40,000
30,000
70,000

Advertising
This manual is related to the following products: