Frymaster HD User Manual

Page 11

Advertising
background image

HIGH EFFICIENCY DECATHLON (HD) SERIES GAS FRYERS

CHAPTER 2: IMPORTANT INFORMATION

2-3

2.5 Rating Plate

This is attached to the inside front door panel. Information provided includes the model and serial
number of the fryer, BTU/hr input of the burners, outlet gas pressure in inches W.C. and whether the
unit has natural or propane gas orifices.

DANGER

Fryers

MUST be connected ONLY to the gas type identified on the attached rating

plate.

2.6 Pre-installation

DANGER

No structural material on the fryer should be altered or removed to accommodate

placement of the fryer under a hood. Questions? Call the Dean Service Hotline at 1-

800-551-8633.


DANGER

Do not connect this appliance to the gas supply before reviewing all information in

this chapter.



A. General: Only licensed personnel should install any gas-fired equipment.

1. A manual gas shut-off valve must be installed in the gas supply line ahead of the fryers for

safety and ease of future service.

2. Dean Decathlon Series gas fryers require 120VAC 60 cycle or 230VAC single-phase 50 Hz

(International) electrical service and are equipped with a 16-3 SJT grounded flexible power
cord for a direct connection to the power supply. Amperage draw for each unit depends on
the accessories supplied with the unit/system.


B. Clearances: The fryer area must be kept free and clear of all combustibles. This unit is design-

certified for the following installations:

1. Commercial installation only (not for household use).

2. Non-combustible floor installation equipped with factory-supplied 6 in. (15 cm) adjustable

legs or 5 in. (13 cm) casters;

3. Combustible construction with a minimum clearance of 6 in. (15 cm) side and 6 in. (15 cm)

rear, and equipped with factory-supplied 6 in. (15 cm) adjustable legs or 5 in. (13 cm)
casters.

Advertising
This manual is related to the following products:

CFD