Installation, Hearth 5" min. combustible material, Floor clearances – FMI MF42ONE User Manual

Page 6

Advertising
background image

www.fmiproducts.com

125636-01A

6

NOTICE: Surface temperatures of adjacent

walls and mantels become hot during opera-

tion. Walls and mantels above the firebox may

become hot to the touch. If installed properly,

these temperatures meet the requirement of the

national product standard. Follow all minimum
clearances shown in this manual.

NOTICE: If your installation does not meet the

minimum clearances shown, you must do one

of the following:

• operate the logs only with the flue damper

open

• raise the mantel to an acceptable height
• remove the mantel

Figure 4 - Minimum Mantel Clearances Without Using Hood

14"

Min.

Combustible

Material

Noncombustible Material

Figure 6 - Minimum Fireplace Clearances If Installed at

Floor Level

Figure 5 - Minimum Mantel Clearances When Using Hood

Minimum Non-
Combustible
Material

Minimum Non-
Combustible
Material Height

Distances to
Underside of
Mantel

Top of Fireplace
Opening

Underside of
Mantel Shelf

12"

(A)

18"

20"

22"

24"

All minimum
distances are
in inches

2

1/2

"

6"

8"

10"

Mantel Shelf

Minimum
Noncombustible
Material

8"
Min.

12"

15" 18" 20"

2

1/2

"

6"

8"

10"

12"

Distances to

Underside of

Mantel

Hood (GA6050

or GA6053)

Top of
Fireplace
Opening

Underside

of Mantel

Shelf

Mantel Shelf

Hearth

5"

Min.

Combustible

Material

Figure 7 - Minimum Fireplace Clearances Above

Combustible Flooring

INSTALLATION

Continued

Determining Minimum Mantel Clearance When Using a
Hood
If minimum clearances in Figure 4, are not met, you must have
a hood. When using a hood there are still certain minimum
mantel clearances required. Follow minimum clearances
shown in Figure 5, when using hood.

INSTALLING DAMPER CLAMP ACCESSORY FOR

VENTED OPERATION

Note: When used as a vented indoor appliance, appliance
must be installed only in a solid-fuel burning fireplace with a
working flue and constructed of noncombustible material.
For Massachusetts Residents Only: Installation of this gas
log set as a vented indoor appliance in the Commonwealth of
Massachusetts requires the damper be permanently removed
or welded in the fully open position.
You must install the damper clamp accessory (to order, see
Accessories, page 21). This will insure vented operation (see
Figure 8). The damper clamp will keep damper open. Instal-
lation instructions are included with clamp accessory.
See chart below for minimum permanent flue opening you
must provide. Attach damper clamp so the minimum perma-
nent flue opening will be maintained at all times.

FLOOR CLEARANCES

A. If installing appliance on the floor level, you must maintain

the minimum distance of 14" to combustibles (see Figure
6).

B. If combustible materials are less than 14" to the fireplace,

you must install appliance at least 5" above the combustible
flooring (see Figure 7).