4 reset modbus port, 5 f-series modbus slave register map – Falcon F3400 User Manual

Page 52

Advertising
background image

www.rletech.com

52

970.484.6510

4

Configuration Menu

Column 1 = System Up Time.

Column 2 = Modbus Master Register Number.

Column 3 = Direction of Packet: OUT = Packet Sent from the F3400/F1000 (Master Request).

Column 4 = Modbus Packet.

4.10.4 Reset Modbus Port

This link allows users to reset the Modbus port so that the contents of the polling registers will

be cleared.

4.10.5 F-Series Modbus Slave Register Map

Table 4.1 Output Registers

Register

Description

Range

40001-40032

Input #1-32 Value

0-65535

40033-40187

Reserved

40188-40193

MAC Address

0-65535

40194-40197

IP Address

0-65535

40198

Model No.

0-65535

40199

Firmware Version

0-65535

40200

Number of Alarms Present

0-65535

40201-40232

Input #1-32 Alarm Bitmap

See Table 4.2

40233-40400

Reserved

40401-40432

Input #1-32 Configuration

See Table 4.3

Table 4.2 Status Flags (Registers 40201-40232)

Bit

Description

00

1 = High1 Alarm

01

1 = Low1 Alarm

02

1 = High2 Alarm

03

1 = Low2 Alarm

04

1 = Digital Alarm

Table 4.3 Status Flags (Registers 40401-40432)

Integer

Description

0

Not Installed

1

Not Configured