Main menu, Table 5.1 main menu commands – Falcon F3400 User Manual

Page 65

Advertising
background image

www.rletech.com

65

970.484.6510

5

EIA-232 Interface

5.3. Main

Menu

All system functions begin in the Main Menu. Two letter commands display information,

execute commands and display submenus for additional inquiry and system configuration

functions.

The Bootloader section is designed for experienced technicians or users

responsible for maintaining the system. Exit immediately if you have not been

trained in the use of the Bootloader commands. Contact RLE for more

information regarding the commands in this section.

Table 5.1 Main Menu Commands

Command Description

Function

CA

Current Alarms

CA displays all active alarms on the master unit. If alarms

are present, the System Status LED is red.

KA

Kill Alarms

KA acknowledges all alarms and terminates all dial-out

communications and network Traps.

TI

Display Date/

Time

TI displays the F3400/F1000's current time and date.

AD

ADC Input

Values

AD allows the user to examine the readings of the 4-20mA

inputs. These readings can be referenced during start-up to

verify gain and offset calculations. Data displayed depends

on the expansion card(s) installed.

MS

Modem

Statistics

MS provides a summary of all modem information.

NS

Network

Statistics

NS displays network and EIA485 statistics including:

network packets received, packets transmitted, and errors.

SC

Main

Configuration

SC displays a submenu that lists all items for system setup

and configuration.

DU

Dump Network

Packets

DU dumps the headers of all network packets received and

sent. Only active until the next command is entered. This

item is for network debugging only and is not normally

enabled.

NT

Network Trace

NT displays troubleshooting messages during the

processing of network packets. Only active until the next

command is entered. Network Trace is for network

troubleshooting only and is not normally enabled.

PING

PING

Allows user to PING another device on the network.

EX

Exit to

Bootloader

EX is used to enter the Bootloader command section. The

unit will stop monitoring the inputs and allow firmware

updates to be loaded. To restore normal operation after

updating firmware, type run and press Enter on the

keyboard, or power the unit off and back on again.

W

ARNING

Advertising