Analog input 4-20ma reference chart, Table a.1 analog input 4-20ma reference chart, Nalog – Falcon F3400 User Manual

Page 79: Nput, Eference, Hart

Advertising
background image

www.rletech.com

79

970.484.6510

A

P P E N D I X

C

HAPTER

0

A

NALOG

I

NPUT

4-20

M

A R

EFERENCE

C

HART

Analog 4-20Ma Gain/Offset Conversion Formula:

Gain = Sensor Range (High Value - Low Value) / 4

Offset = Sensor Low Value - Gain

Example: TH140 Humidity

Gain = (High Value (100) -Low Value (0)) / 4 = 25

Offset = (Sensor Low Value (0) - Gain (25)) = -25

Table A.1 Analog Input 4-20mA Reference Chart

RLE

Product

Number

Transducer Type

Range

Gain

Offset

TEMPERATURE

TH140

Temperature (Display in Deg F)

50°F - 95°F

11

39

Temperature (Display in Deg F

32°F - 122°F

22

11

Temperature (Display in Deg C)

10°C - 35°C

6

4

Temperature (Display in Deg C

0°C - 55°C

13

-13

Humidity

0% - 100% RH

25

-25

T120

Temperature (Display in Deg F)

50°F - 95°F

11

39

Temperature (Display in Deg F)

32°F - 122°F

22

11

Temperature (Display in Deg C)

10°C - 35°C

6

4

Temperature (Display in Deg C)

0°C - 50°C

13

-13

CURRENT

CT55

Current

0 - 5 Amps
0 - 55 Amps

1
13

-1
-13

Advertising
This manual is related to the following products: