2.4. F3400/F1000

Wiring

RLE Technologies recommends an 18AWG stranded copper wire for connection from each

monitored point to a terminal block (TB) connection on the F3400/F1000. RLE recommends no

more than 500 feet (152.4m) of wire at this specification. If longer runs are needed, please

contact RLE Technologies for application guidance. Shielded twisted pair wiring is

recommended for analog signal transmitters being wired outside of conduit runs and dropped

ceiling applications.

2.4.1 Power Supply and Ground Connections

Connect an 18AWG ground wire from the ground terminal to a suitable earth ground. Plug the

wall adapter into P1 and a UPS outlet as shown below. The wall adapter has a five foot power

cord. RLE Technologies recommends powering the F3400/F1000 from a UPS supply to allow

the F3400/F1000 to send alarm notification during a power outage.

Figure 2.1 24 VDC Power Supply Connection