3 loading configuration data via tftp client – Falcon F3400 User Manual

Page 77

Advertising
background image

www.rletech.com

77

970.484.6510

8

Upgrading Firmware and Managing Configuration Data

8.2.3 Loading Configuration Data via TFTP Client

Before the configuration can be loaded onto other F3400/F1000s, it must be checked for

accuracy. Blank spaces or unwanted characters, such as the “Press <enter> to download the

file” text, may be saved into the beginning of the configuration file. Open the file in Notepad

and examine the first few lines. Delete any characters that were accidentally embedded into the

file.

1

Verify that your PC is connected to the F3400/F1000 over the LAN and that port 69 is open

between your PC and the Falcon.

2

Open your TFTP client. Configure the client as follows.

a

Host = F3400/F1000 IP Address

b

Port = 69

c

Block Size = 64, 128, 256, 512, or 1024

Note

The file must be sent in BINARY (not ASCII).

3

The file name of the configuration being loaded must contain the .cfg extension.

4

Send or PUT the file. After a few seconds, the TFTP software should indicate when it is

complete.

5

Configurations are now loaded onto the replacement F3400/F1000. View the Falcon

webpages to verify that the configurations are as expected.

8.2.4 Loading Configuration Data via EIA232 COM1 Port

(X-Modem)

Before the configuration can be loaded onto other F3400/F1000s, it must be checked for

accuracy. Blank spaces or unwanted characters, such as the “Press <enter> to download the

file” text, may be saved into the beginning of the configuration file. Open the file in notepad

and examine the first few lines. Delete any characters that were accidentally embedded into the

file.

1

To load settings, go to the F3400/F1000 onto which the configuration will be loaded. Log

into the F3400/F1000 (COM1) through HyperTerminal (Terminal Emulation Program).

Navigate to the Load/Save Configuration Data Menu under the Main Configuration

Menu.

2

Select option 2 (

Load Xmodem 1K

) from the Load/Save Configuration Menu and press

ENTER. Then select Transfer/Send File from the menu at the top of the HyperTerminal

screen.

3

Select the 1K X-Modem protocol. Locate the correct configuration file under Filename

(Browse), select Open, and then select the Send button.

4

Wait until the Upload is completed and enter X to exit the Load/Save Configuration Menu.