Friedrich HAZARDGARG R-410A User Manual

Page 18

Advertising
background image

Restricted Refrigerant System

Troubleshooting a restricted refrigerant system can be

difficult. The following procedures are the more common

problems and solutions to these problems. There are two

types of refrigerant restrictions: Partial restrictions and

complete restrictions.
A partial restriction allows some of the refrigerant to

circulate through the system.
With a complete restriction there is no circulation of

refrigerant in the system.
Restricted refrigerant systems display the same symptoms

as a “low-charge condition.”
When the unit is shut off, the gauges may equalize very

slowly.
Gauges connected to a completely restricted system will

run in a deep vacuum. When the unit is shut off, the gauges
will not equalize at all.
A quick check for either condition begins at the evaporator.

With a partial restriction, there may be gurgling sounds

at the metering device entrance to the evaporator. The

evaporator in a partial restriction could be partially frosted

or have an ice ball close to the entrance of the metering

device. Frost may continue on the suction line back to the

compressor.
Often a partial restriction of any type can be found by feel,

as there is a temperature difference from one side of the

restriction to the other.
With a complete restriction, there will be no sound at the

metering device entrance. An amperage check of the

compressor with a partial restriction may show normal

current when compared to the unit specification. With a

complete restriction the current drawn may be considerably

less than normal, as the compressor is running in a deep

vacuum (no load.) Much of the area of the condenser will

be relatively cool since most or all of the liquid refrigerant

will be stored there.
The following conditions are based primarily on a system

in the cooling mode.

17

Advertising