Troubleshooting – Friedrich HAZARDGARG R-410A User Manual

Page 25

Advertising
background image

TROUBLESHOOTING

Problem

Possible Cause

Possible Solution

Possible Solution

Possible Solution

Possible Solution

Possible Solution

Unit does not run

Power disconnected.

Check power source.

Branch circuit fuse blown or circuit

breaker tripped.

Replace fuse, reset breaker. If repeats, check fuse

or breaker size. Check for shorts in unit wiring and

components.

Loose or disconnected wiring at

switch.

Check wiring & connections. Connect per wiring

diagram.

Inoperative switch (On-Off).

Test for continuity, 3 and 2, 5 and 6. If bad,

replace.

Problem

Possible Cause

Evaporator coil

freezes up

Dirty filter.

Clean as recommended in Owner's Manual.

Restricted airflow.

Check for dirty or obstructed coil clean as

required.

Inoperative thermostat.

Test for shorted thermostat or stuck contacts.

Short of refrigerant.

De-ice coil and check for leak.

Partially restricted capillary.

De-ice coil. Check temperature differential

across coil. Touch-test coil return bends for same

temperature. Test for low running current.

Inoperative fan motor.

Test fan motor & replace if inoperative.

Problem

Possible Cause

Compressor runs

continually. Does

not cycle off.

Excessive heat load.

Test cooling performance of unit. Unit undersized.

Restriction in line.

Check for partially iced coil. Check temperature

split across coil.

Refrigerant leak.

Check for presence of oil on silver soldered

connections. Check for partially iced coil. Check

split across coil. Check for low running amperage.

Thermostat contacts stuck.

Check operation of thermostat. Replace if contacts

remain closed.

Incorrect thermostat setting.

Set to correct setting.

Problem

Possible Cause

Thermostat

does not turn on

compressor

Loss of charge in thermostat bulb.

Replace thermostat.

Thermostat contacts open.

Test for continuity at terminals 1 and 2. Replace if

defective.

Incorrect wiring or loose wires.

Connect per wiring diagram. Tighten loose wires.

System switch open.

Test for continuity at switch terminals 2 and 3.

Problem

Possible Cause

Thermostat

does not turn off

compressor

Thermostat set at coldest point

Adjust.

Thermostat contacts stuck.

Disconnect power to the unit. Remove cover of

thermostat and check if contact is stuck, if so

replace thermostat.

Switch (On-Off) shorted.

Test switch for open contacts at terminals 2 and 3

with switch in “Off” position.