Important multiple venting – Fedders FV95A090 User Manual

Page 23

Advertising
background image

COMBUSTION AIR

EXHAUST

8”

12”

2”

12” CLEARANCE ABOVE GRADE OR

HIGHEST ANTICIPATED SNOW LEVEL.

D

E

F

G

H

I

J

K

L

A

B

C

COMBUSTION AIR

EXHAUST

8”

12”

2”

12” CLEARANCE ABOVE GRADE OR

HIGHEST ANTICIPATED SNOW LEVEL.

D

E

F

G

H

I

J

K

L

A

B

C

B

C

TOP VIEW

INTERIOR

EXTERIOR

C

D

J

A

B

I

A

B

E

D

C

F

H

A

E

E

D

B

Vertical Combustion Air Termination

The combustion air termination is a pair of 2” medium or
long sweep 90° elbows pointing downward to prevent rain
from entering the combustion air intake piping.

If 3” piping is used, it should be reduced to 2” within 18”
of the point where the pipe penetrates the roof. The ter-
mination inlet must be positioned within 3” of the com-
panion exhaust piping.

The combustion air inlet must be located a minimum of
12” above the anticipated snow level, and 12” below the
exhaust outlet.

Vertical Exhaust Vent Termination

The exhaust vent may terminate in a vertical venting
configuration through the roof.

No termination fitting is required if venting vertically
through a roof. The end of the exhaust pipe must be 12”
higher than the entrance of the combustion air intake
terminal.

The exhaust pipe extending through the roof must extend
a minimum of 18” above any obstruction within an 18”
horizontal distance.

VERTICAL TERMINATION OF
COMBUSTION AIR

AND EXHAUST VENT

A

B

C

TOP VIEW

INTERIOR

EXTERIOR

C

D

J

A

B

I

A

B

E

D

C

F

H

A

A

C

D

E

E

D

B

B

C

D

F

F

B

E

G

A

A

B

D

A

D

G

WARNING

COMMON VENTING IS PROHIBITED

If two of these furnaces are to be installed in close proximi-
ty, the combustion air intake and exhaust terminations may

If more than two furnaces are being installed in close prox-
imity, each additional combustion air intake and exhaust
termination set must be installed a minimum of 4 feet
apart. This is an exception to the 10 foot requirement men-
tioned in the “Location” section on the previous page. If
using the concentric venting kits, two terminals may be
centered 12 inches apart.

When installing multiple furnaces in close proximity,
each requires dedicated combustion air and exhaust
venting.

IMPORTANT

MULTIPLE VENTING

21

Figure 10

be installed as shown in Figures 10.