Important, Troubleshooting – Fedders FV95A090 User Manual

Page 41

Advertising
background image

DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE
FURNACE BEFORE ATTEMPTING THIS MAINTENANCE
PROCEDURE. FAILURE TO DO SO CAN CAUSE
ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR
LOSS OF LIFE.

All electrical connections should be examined to ensure that
they are tight and corrosion free. Repair any connections
that have become loose or corroded.

Furnace Operation

The furnace should be cycled during the annual inspection
and servicing to:

1. Test all safety related controls.

2. Determine that the temperature rise falls within the

range shown on the appliance rating plate.

3. Ensure that the burner ignition is smooth and that the

flames are smooth soft blue, and not impinging on the
heat exchanger.

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation.

Always verify proper operation after servicing.

FIELD SUPPLIED AND INSTALLED OPTIONAL
ACCESSORIES
Electronic Air Cleaner

The integrated furnace control has provisions to supply
power and control an electronic air cleaner rated at 120vac,
1.0 amp max.

Line voltage for an electronic air cleaner may be picked up
from the "EAC-N". 120 volt power will be available at these
terminals whenever the circulating fan is operating in the
heating or cooling modes.

The integrated furnace control has provisions to supply
power and to control a line voltage humidifier or the
primary of a 120 / 24 volt humidifier step down transformer,
rated at 120vac, 1.0 amp max.

Line voltage for a humidifier may be picked up from the
"HUM-H" terminal and from the "HUM-N" terminal. 120
volt power will be available at these terminals whenever
the circulating fan is operating in the heating mode.

Electrical

ALL WIRING INSIDE THE FURNACE MUST HAVE A
MINIMUM TEMPERATURE RATING OF 105C.

All HUM (humidifier) and EAC (electronic air cleaner)
terminals are 120v. Do not directly connect 24v
equipment to them.

IMPORTANT

All furnace and furnace accessory wiring shall conform
to the temperature limitations of 63°F (35°C) rise.

IMPORTANT

WARNING

CAUTION

WARNING

heat and make a retrial for high every 5 or 10 minutes.

switch does not pull in the controller will continue in low

finished) and during the trial for ignition the high pressure

If there is a demand for high heat (low heat firing period is

The fourth scenario:

heat.

the gas low the flame noise sounds deceptively like high

heat should free it. Note: When the inducer is in high and

gas valve to low. If there is ice in the vent the continuous

period, the high pressure switch makes, the gas valve will

long as the low pressure switch is made). If, during this

switch, the unit will stay in low heat and high inducer (as

the next trial for high fails to make the high pressure

If the low heat fails after the warm-up period, and when

The third scenario;

for pressure switch failed to close.

exchanger drain tube the furnace will cycle and flash code

the igniter or gas on. If there is an air trap in the heat

voltage. If there is a blocked drain the furnace will not turn

a combination of high wind and long vent length and low

the failure of the low heat is temporary and may be due to

then after the warm-up period go to high heat. Most likely

controller will wait 3 minutes before ignition retrial and

If the low heat fails after the warm-up period, the

The second scenario;

inducer until the high pressure switch makes.

fails to make, the furnace will run in low gas and high

demand for heat is high and the high heat pressure switch

a single stage thermostat, or with a two stage T-stat the

• if, after the warm-up period and the low heat period with

Scenario one:

to supply heat in one of three alternate firing scenarios.

h

before high heat. If there is a problem with high or low

thermostat option, there is a selectable low heat period

or inducer to heat demand. With the single stage

and after a 60 second warm-up period adjusts either the gas

inducer (only the low pressure switch is required to make)

The controller ignites the furnace in low heat and high

Troubleshooting

will aid in trouble shooting.

39

Page 41, Table 9, Page 42, Table 10 and Figure (trouble shooting)

eat the UTEC 1170-25 controller will attempt to continue

Humidifiers/ Electronic Air Cleaners

switch to high. A loss of high pressure switch will force the

Advertising
This manual is related to the following products: