Fireplace installation – FMI S42 User Manual

Page 5

Advertising
background image

www.fmiproducts.com

111099-01L

5

DRAIN PAN (DP42)

For outdoor installations, the fireplace enclo-

sure must allow for adequate drainage and

fresh air ventilation. It is recommended that

a sealed, corrosion resistant catch pan with

provision for drainage be installed under the

fireplace within the fireplace enclosure (see

Accessories, page 16).

HEARTH EXTENSION

A hearth extension projecting a minimum of

20" in front of and a minimum of 12" beyond

each side of the fireplace opening is required

to protect combustible floor construction

in front of the fireplace. Fabricate a hearth

extension using a material which meets the

following specifications: a layer of noncom-

bustible, inorganic material having a thermal

conductivity of K=0.84 BTU IN/FT, HR. F (or

less) at 1" thick. For example, if the material

selected has a K factor of 0.25, such as glass

fiber, the following formula would apply:

0.25 x 1.0" = 0.30" thickness required

0.84

Thermal conductivity "K" of materials can be

obtained from the manufacturer or supplier of

the noncombustible material. If the hearth ex-

tension is to be covered, use noncombustible

material such as tile, slate, brick, concrete,

metal, glass, marble, stone, etc. Provide a

means to prevent the hearth extension from

shifting and seal gap between the fireplace

frame and hearth extension with a noncom-

bustible material (see Figure 3).

FIREPLACE INSTALLATION

Figure 3 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front

Raised Hearth

Fireplace Front

Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth

Extension

WARNING: Hearth extension

is to be installed only as shown

in Figure 3.

MANTELS

A mantel may be installed if desired (see

Figure 4). Woodwork such as wood trims,

mantels or any other combustible material

projecting from front face must not be placed

within 12" of the fireplace opening. Combus-

tible materials above 12" and projecting more

than 1

1

/

2

" from the fireplace must not be

placed less than 15" from top opening of the

fireplace (NFPA STD 211, Sec. 7-3.3.3).
Mantels or any other combustible material

also may come up to the side edge of the

black metal face of the fireplace just as long

as the projection from the front face fall within

the limit shown in Figure 4.

12

1

/

4

" Ref.

6"

Ref.

15" Min.

12" Min.

1

1

/

2

" Max.

3" Nom.

33°

Combustible

Material

Safe

Zone for

Projection of

Combustible

Materials

Fireplace Opening

Upper

Section of

Fireplace

Figure 4 - Mantel Clearances to

Combustible Material

FIREBOX

SAFE ZONE

Top View of Fireplace

2" Max.

3.0"

Min. to

Perpendicular

Side Wall

12"

8.0"

33°

Combustible

Material Must

Not Overlap

Front Face

Advertising