LC-1000 Lube System Controller

Sample LC-1000 Program for Bi-Flo (Dual Line) Systems

31 Point Bi-Flo (Dual Line) System

DESCRIPTION

System Lube Volume: 6.0 cu in (99 cc) per hour
Bi-Flo Motor Driven Pump Used: 8.6 cu in (141 cc)
per minute.
Note 1: Requires a Motor Starter
Note 2: Requires a hydraulic reverser with

cycle switch.

Cycle Interval 15 Minute (1/4 hour) Used
Volume per Lube Cycle: 6.0 cu in/4 = 1.5 cu in/15
minute.
Cycle Switch Transitions (2 transitions/cycle)
x 1 = 2
Pump Run Time per Lube Cycle: 1.5 cu in/
8.6 cu in = .17 min (10.4 second)
Monitor Time: 10.4 sec x 2 (safety factor) = 20.8
second (use 21 second).



4. “CYCLE” (Cycle Switch Transitions)

a) Press “ENTER” Key;

CYCLE (switch transitions) blinks

b) Use S Key and X Key to select 02 (02

cycle switch transitions = 1 System cycle)

c) Press “ENTER” Key to accept value;

”PUMP” Icon blinks

5. “PUMP ON” (Pump Duty-Pulsed/Non-Pulsed)

a) Press “ENTER” Key

"PUMP" (pulsed on time) blinks

b)

Use

S Key and X Key to set

”ON TIME” TO 00 (Non- pulsed output)

c) Press “ENTER” Key to accept value;

LCD returns to “DISPLAY” mode

Programming is now complete. To verify lube sequence,
initiate a manual lube cycle by pressing “MANUAL RUN”
button.

NOTE 1: If half cycle Bi-Flo (Dual Line) operation is desired,

select 01 (one switch transition) in step 4b.

NOTE 2: If a single cycle pump is used in conjunction with a

Bi-Flo Reverser, enter “03” in Step 5b for pulsed

pump output (3 second "ON", 3 second "OFF").

PROGRAMMING

1. Initiate Programming Mode

a) Press “PRGM” Key – “ON” Icon blinks

2. “ON” (Monitor Period)

a) Press “ENTER” Key – ON TIME/COUNT
blinks

b) Use S Key and X Key to set Monitor (“ON”)

Time to 0021

c) Press “ENTER” Key to accept value;
“SEC/MIN/HR/CNT”

blinks

d) Use S Key to scroll through choices;

select ” SEC”

e) Press “ENTER” Key to accept choice;

“OFF” Icon blinks

3. “OFF” (Pause Time)

a) Press “ENTER” Key –
OFF

TIME/COUNT

blinks

b)

Use

S Key and X Key to set

“OFF TIME” to 0015

c) Press “ENTER” Key to accept value;
"SEC/MIN/HR/CNT"

blinks

d) Use S Key to scroll through choices;
select

“MIN”

e) Press “ENTER” Key to accept choice;

“CYCLE” Icon blinks

PUMP AND
RESERVOIR

LUBRICATION

POINTS

INDICATORS

BI-FLO

VALVES

REVERSER

VENT LINE

CYCLE SWITCH