Pg. 9-11, Installation instructions for, Assemble roof curb – Greenheck Fan Outdoor Air Ventilator User Manual

Page 9: Install ductwork, Locate and cut roof opening, Install curb

Advertising
background image

9

Installation Instructions for:

CURB MOUNTING*
NV-90 and NV-120

*For installations using Greenheck's

optional roof curb.

1. Assemble Roof Curb

Curbs are shipped knockdown and require assembly
by others. Assembly instructions are also included
with curb.

Assemble curb sections as shown using hex bolts and
lock nuts supplied with curb.

Detail shown is typical for all four corners.

Recommended

Roof Opening

(36" x 36")

103

1

/

2

43

1

/

4

40

5

/

8

24

1

/

4

4

1

/

2

Roof Curb

81

3

/

16

4. Install Ductwork

The following chart shows the duct sizes and straight
lengths recommended for optimal performance (AMCA
Publication 201-90). Using duct sizes less than
recommended lengths will affect fan performance. Good
duct installation practices should be followed for the
remaining ductwork.

Roof Opening

B

C

D

Ductwork
by Others

Roof Curb

A

Straight

A

B

C

D

Duct Length

NV-90

24

9

3

/

8

24

30

1

/

4

81

NV-120

26

9

1

/

2

26

29

1

/

4

96

Duct Locations:

2. Locate and Cut Roof Opening

When locating unit, make sure there is room to access unit
from all sides. Make sure inlet of this unit is located well
away from exhaust fans.

Roof Opening for NV-120 and NV-90 = (A) 36" x (B) 36"

3. Install Curb

Located curb over roof opening with dimensions shown to
the right and fasten in place.

Check that diagonal dimensions are within
± 1/8" of each other and adjust as necessary. Shim as
required to level.

Advertising