4. TECHNICAL CHARACTERISTICS

22

DBF Breaker Failure Protection

GEK-106168E

4.2. TECHNICAL CHARACTERISTICS

MECHANICAL

•

Metal 19” rack case, 2 units high

•

IP51 Protection (as per IEC 529)

•

Local HMI: LCD (2 rows, 16 characters) and 20 key keyboard

•

Rear connection for wiring: 4 blocks, 12 terminals each (6 blocks when optional expansion board)

•

Dimensions: 437 x 164 x 88 mm

•

Weight: Net 6 kg. Shipping 7 kg.

ELECTRICAL

•

Frequency:

50 or 60 Hz (selectable by setting)

•

Rated current:

1 or 5 A (different models)

•

DC Power Supply

48/125 Vdc or 110/250 Vdc (different models)

•

Operational range

80% to 120% of rated values

•

Digital Input Voltage

For standard models: 48-125, 110-250 VDC
(according to selected model). For special models,
please refer to section 4.1.1.

•

Thermal Capacity
Current circuits

- Permanent

4 x In

- 3s duration

50 x In

- 1 s duration

100 x In

•

Temperature ranges

-Operation

-20º C to + 55ºC

-Storage

-40ºC to + 70ºC

•

Humidity

Up to 95% without condensation

•

Trip contacts:

AC
-Continuous Capacity

16A

-Rated Breaking Capacity

4000VA

-Make

25A for 4 sec

-Operating Time

8 ms or less

DC Breaking Capacity
- Resistive

9A at 30V

- Resistive

0.65A at 100V

- Inductive(L/R=40 ms)

0.5A at 30V

•

Burden

-Current circuits

0.5 VA at I

r

= 5 A

0.1 VA at I

r

= 1A

•

Consumption:

-At DC rated voltage

12 W idle state
16 W all relays activated

-Digital inputs

8 mA (1 W at V

rated

= 125 VDC)

•

Accuracy

-Current

5%

-Time

5% or 30ms (whichever is greater)

- Error index

Class E-5 as per IEC 255-4

•

Repeatability

-Operating value

1%

-Operating time

2% or 30 ms (whichever is greater)