1. GENERAL DESCRIPTION AND APPLICATION

GEK-106168E

DBF Breaker Failure Protection

1

1.

1.

1.

1.

GENERAL DESCRIPTION AND APPLICATION

GENERAL DESCRIPTION AND APPLICATION

GENERAL DESCRIPTION AND APPLICATION

GENERAL DESCRIPTION AND APPLICATION

1.1. GENERAL DESCRIPTION

The DBF system is a microprocessor based breaker failure protection, control and measurement unit that has
different algorithms to allow its use on a wide range of applications in power systems.

The functions and information management of the unit can be performed remotely (computer connected to the
serial port RS232, fiber-optic or modem) or locally using the man-machine interface (HMI), which includes a 20
keys keypad, and a two line liquid crystal display (LCD) on the front of the relay.

The system provides the following functions:

a) Protection

•

Low current level breaker failure protection, following a single or three phases initiation, with up to
two time delayed steps.

•

High current level breaker failure protection, following a two/three (selectable by setting) phases
initiation.

•

No current breaker failure protection, following a two/three (selectable by setting) phases initiation.

•

Breaker internal arc detection.

b) Monitoring

•

Current measurements for each phase and ground.

•

Breaker status

•

16 fully configurable LED indicators

•

One fixed relay status LED

•

Breaker health monitoring (

Σ

I2 t).

•

Built-in self-check functions.

c) Analysis:

•

Event recorder

•

Oscillography

d) Control:

•

3 settings’ tables

•

Time synchronization using the communications program, the IRIG-B input or the HMI (keypad and
display).

•

Configurable inputs and outputs.

•

User can build logic schemes using AND, OR and NOT gates and the internal digital signals of the
relay.