Test Sequence per VDE 0701

Select connection, select test regulation VDE 0701 part 1 or 200, classify the DUT (SC I, II or III), part 1: extension cable X/– (with/without)

Visual inspection

OK?

SC I: RPE

OK?

I

L

OK?

Short-circuit

at DUT?

Test
OK?

Yes/No

No

Yes

Display results, save/print report

Yes

No

Yes

No

No

Test
OK?

Framed with dashed line:
The test is only run if it has been activated in
the initial program window, or in the Setup
menu under Sequence ...

Switch line voltage to test socket, start function test

Start

function test

Safety Class I only: Contact all exposed, conductive parts with the
probe. The test can be repeated as often as desired for various
protective conductor parts with the manual sequence*

* If it is not clear whether or not all

exposed, conductive parts are
connected to one another or to the
protective conductor, testing can be
performed in the manual mode.

Switch DUT on

RISO+I

EL

OK?

or