Energy Recovery Ventilator

Factory Set Points

Variable Frequency Drives (VFDs) for the blowers are
factory setup to operate in one of the three following
modes:

Modulating: 0-10 VDC signal wired in the field by

others varies the speed of the blower between 30
and 60Hz

Multi-speed: Digital contact closures by others

command the VFD to run at multiple speed settings:
 t4$UP4%SJWFSVOTBU)[
 t4$UP4%SJWFSVOTBU)[

CO2 Sensor: A digital contact closure from an

optional factory provided CO2 sensor sends the

VFD to high or low speed depending on CO2 ppm

levels at the sensor.

The terminal locations for Modulating (option 1) and
Multi-speed (option 2) are shown on the left. Most
of the set points in the VFDs are Yaskawa factory
defaults. However, a few set points are changed at
Greenheck and are shown in the tables on the next
page. These settings are based on the VFD mode
selected.

To gain access to change set points on the V1000 and
+ESJWFT QBSBNFUFS"OFFETUPCFTFUBUiw
To prevent access or tampering with drive settings on
either drive, change parameter A1-01 to “0”.

Drive Operation

SC to S1 contact for On/Off

A1 (0-10 VDC) referenced to AC. Can use +15 VDC

from +V

Variable Frequency Drives for Energy Recovery Blowers

Optional factory installed, wired, and programmed variable frequency drives (VFDs) may have been provided
for modulating or multi-speed control of the blowers. One VFD is provided for each blower (supply air and
FYIBVTU 5IF7'%TQSPWJEFEBSFFJUIFS:BTLBXBNPEFM7PS+3FGFSUPUIFUBCMFTJOUIJTTFDUJPOGPS
factory settings and field wiring requirements. Refer to the unit control center for unit specific wiring diagram (an
example wiring diagram has been provided in this manual for reference). When making adjustments outside of
the factory set points, refer to Yaskawa VFD instruction manual, which can be found online at www.drives.com.
For technical support, contact Yaskawa direct at 1-800-927-5292.

MA MB MC

RP

H1

SC

HC

S7

S6

S5

S4

S3

S2

S1

MP

AC

AM

AC

+V

A2

A1

PC

P2

P1

IG

S-

S+

R-

R+

V1000

MA MB MC

AC

AM

AC

+V

A1

SC

S5

S4

S3

S2

S1

J1000

OPTION 1 - 0-10 VDC CONTROL

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

USER TO PROVIDE ISOLATION AS REQUIRED

FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.

WIRED TO A1 (+) AND AC (COMMON)

0-10 VDC CONTROL SIGNAL (BY OTHERS)

10 VDC=60 Hz

0 VDC=30 Hz

A1 AC

FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL

OPTION 2 - MULTI SPEED CONTROL

S5

S4

SC

NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 60 Hz.

DRIVE SPEED = 40 Hz.

S4 TO SC CONTACT CLOSED (BY OTHERS)

S5 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 30 Hz.

TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.
PARAMETER n01 CHANGE TO 1

PARAMETER n22 FOR NEW 40Hz SETTING

PARAMETER n21 FOR NEW 60Hz SETTING

PARAMETER n23 FOR NEW 30Hz SETTING
PARAMETER n01 CHANGE TO 0

USER TO PROVIDE CONTACTS AND ISOLATION
AS REQUIRED

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL