17

Energy Recovery Ventilator

Parameter

4FUUJOHo+

A1-01

Access Level

2

b1-17

VFD Auto Start

1

C6-02

Carrier Frequency

2

d2-01

Ref Upper Limit

100% or 66%*

d2-02

Ref Lower Limit

5%

E2-01

Motor Rated FLA

Motor FLA

E2-03

Motor No-Load Current

Must be less than

FLA

H1-02

Multi-Function Input

(Terminal S2)

6

H2-01

Multi-Function Output

(MA, MB, MC)

5

Economizer Signal Source
(0-10 VDC)

Setting

Honeywell

Module

Carel

Controller

H3-03

Analog Frequency Reference

(Gain)

0

100

H3-04

Analog Frequency Reference

(Bias)

99

0

L1-01

Elect Thermal Overload

2

L4-01

Frequency Detection Level

20

A1-01

Access Level

0

*36 inch wheel is 66% (40 Hz). All other wheels are 100% (60 Hz).

MODULATING CONTROL FOR FAN SPEED

(0-10 VDC)

Parameter

Setting

V1000

+

A1-01

Access Level

2

2

b1-17

VFD Start-Up Setting

1

1

C1-01

Acceleration Time

30 sec.

30 sec.

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

d2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

FLA

Motor

FLA

H3-04

Terminal A1 Bias

50%

50%

A1-01

Access Level

0

0

MULTI-SPEED CONTROL FOR FAN SPEED

(1/3 OR 1/2 SPEED REDUCTION)

Parameter

Setting

V1000

+

A1-01

Access Level

2

2

b1-01

Reference Source (Frequency)

0

0

b1-17

VFD Start-Up Setting

1

1

C1-01

Acceleration Time

30 sec.

30 sec.

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

d1-01

Frequency Reference 1

60 Hz

60 Hz

d1-02

Frequency Reference 2

40 Hz

40 Hz

d1-03

Frequency Reference 3

30 Hz

30 Hz

d1-04

Frequency Reference 4

60 Hz

60 Hz

d2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

FLA

Motor

FLA

H1-04

Multi-Function Input Sel 4

(Terminal S4)

3

3

H1-05

Multi-Function Input Sel 5

(Terminal S5)

4

4

H1-06

Multi-Function Input Sel 6

(Terminal S6)

5

NA

H3-10

A2 Not Used

F

NA

A1-01

Access Level

0

0

CO2 SENSOR CONTROL FOR FAN SPEED

(1/2 SPEED WHEN C02 DROPS BELOW 700 PPM)

Parameter

Setting

V1000

+

A1-01

Access Level

2

2

b1-01

Reference Source (Frequency)

0

0

b1-17

VFD Start-Up Setting

1

1

C1-01

Acceleration Time

30 sec.

30 sec.

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

d1-01

Frequency Reference 1

60 Hz

30 Hz

d1-02

Frequency Reference 2

30 Hz

60 Hz

d2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

FLA

Motor

FLA

H3-10

A2 Not Used

F

NA

A1-01

Access Level

0

0

Factory Set Points -

continued

Resetting the drive to factory defaults
To reset the drive back to Greenheck factory defaults
go to parameter A1-01 and set it to “2”. Then go to
A1-03 and change it to “1110” and press enter. The
drive is now reset back to the settings programmed at
Greenheck.

Variable Frequency Drives for Energy
Recovery Wheel

Optional factory installed VFD for the energy recovery
wheel is programmed at the factory per the settings
shown below for economizer and frost control modes.
5IF7'%QSPWJEFEJTB:BTLBXBNPEFM+3FGFS
to the VFD instruction manual that ships with the unit
when making adjustments.