Greenheck Fan Duct Smoke Detector none User Manual

Installation instruction, Detail 1, For rrl (resettable/reusable link) on

Advertising
background image

Gasket

1 Req’ d

J-Box Cover

1 Req’ d

#10 1/2 in.

Te k

Scr ew

2 Req’ d

J-Box

1 Req’ d

RRL

Req’ d

3

2

4

6

Steps to install an RRL in a Fire Smoke Damper:

1) Drill/Saw a 3 5/8 in. (92mm) diameter hole in sleeve (Detail

2).

2) Insert OCI unit through hole in sleeve (round end inside).
3) Place 4 x 4 in. J-Box over the flange of the OCI unit and

align holes.

4) Mount control box to sleeve/sideplate with #10-16 x 3/4 in.

(19mm) TEK screw (or equivelant) (Detail 1).

5) Complete wiring and install J-Box cover.

Part Number 459840

Detail 1

Installation Instruction

for RRL (resettable/reusable link) on

FSD, SSFSD, SEFSD, IMO series

Combination Fire Smoke Dampers