background image

Model SMD-401M meets the requirements for smoke

dampers established by:

National Fire Protection Association

NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
ICBO Uniform Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#3230-0981:108)

“UL CLASSIFIED (see complete marking on

product)”

“UL CLASSIFIED to Canadian safety standards

(see complete marking on product)”

Standard 555S (Listing #R13317)

APPLICATION

Model SMD-401M is a class I leakage rated modulating smoke

damper. The model SMD-401M serves the function of

both a control damper and smoke damper. High strength airfoil

blades ensure the lowest resistance to airflow in HVAC systems

with velocities to 2000 fpm (10.2 m/s ) and 4 wg (1 kPa). Model

SMD-401M may be installed vertically (with blades running

horizontal) or horizontally and is rated for airflow and leakage in

either direction.

RATINgS

Leakage Class:

I

Operational Rating: Actual ratings are size dependent.

Max. Velocity:

up to 2000 fpm (10.2 m/s)

Max. Pressure:

4 in. wg (1 kPa)

Temperature:

250°F (121ºC) with all actuators.

STANDARD CONSTRUCTION

Frame:

5 in. x 1 in. (127mm x 25mm)

galvanized steel hat channel with

reinforced corners. A low profile

head and sill are used on sizes

less than 17 in. (432mm) high to

maximize free area and

performance.

Blades:

Airfoil shape constructed of

heavy gauge extruded aluminum.

Structural reinforcement through

the entire length.

Seals:

Extruded silicone rubber blade

seals. Flexible stainless steel

jamb seals.

Linkage:

Concealed in jamb.

Axles:

1

2

in. (13mm) dia. plated steel.

Bearings:

Bronze sleeve type.

SIzE LIMITATIONS:

Minimum Size:

8 in. W x 8 in. H

(203mm W x 203mm H)

Maximum Size:

Single Section:

36 in. W x 36 in. H

(914mm W x 914mm H)

Multi Section:

144 in. W x 36 in. H

(3658mm W x 914mm H)

Optional Features:

• Galvanized steel sleeves.
• Stainless steel bearings
• OCI (Open closed indication switches)
• Electric or pneumatic actuators to accomplish smoke

management and system functions.

• POC Retaining angles
• Smoke detector
• Momentary switch
• Transitions (R, C, O)
• Sealed transitions and sleeves

SMD-401M

Smoke Dampers

Extruded Airfoil Blades

UL 555S Leakage Class I

*W&H dimensions furnished approximately

1

/

4

in. (6mm) undersize.

(Add sleeve thickness for overall sleeved damper dimension)

Right hand drive is shown. Left hand drive is available upon request.