Transitioned Damper Dimensions

When a fire/smoke damper is being used in conjunction with round or oval ductwork, the SMD-401M can be supplied in a

factory sleeve with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the duct dimensions.

Drawings below show overall damper size.

* These dimensions are furnished approximately

1/4

in. (6mm) undersize, except round and oval dimensions which are

approximately

1/8

in. (3mm) undersize.

Ts = (2)(Sleeve Thickness)

Smoke Dampers meeting the following specifications

shall be furnished and installed where shown on plans

and/or as described in schedules. Dampers shall meet

the requirements of NFPA 90A, 92A, 92B, 101 and 105 and

further shall be tested, rated and labeled in accordance with

the latest edition of UL Standard 555S. Smoke dampers

shall be of low leakage design qualified to UL 555S Leakage

Class I.

Each damper /actuator combination shall have a UL555S

elevated temperature rating of 250°F (121ºC) minimum and

shall be rated to operate at maximum design airflow at its

installed location. Each damper shall be supplied with an

appropriate actuator installed by the damper manufacturer

at the time of damper fabrication. Damper actuator shall be

(specifier select one of the following) electric type for 24 volt

operation.

Damper blades shall be hollow extruded aluminum airfoil

type with structural reinforcing tube running full length of

each blade. Damper frame shall be galvanized steel formed

into a structural hat channel shape with reinforced corners.

Bearings shall be sintered bronze sleeve type rotating in

extruded holes in the damper frame. Blade edge seals

shall be silicone rubber designed to inflate and provide a

tighter seal against leakage as pressure on either side of

the damper increases. Jamb seals shall be stainless steel

compression type. Damper must be rated for mounting

vertically (with blades running horizontal) or horizontally and

be UL 555S rated for leakage and airflow in either direction

through the damper.

The basis of design is Greenheck Model SMD-401M.

Specifications

D* + 2 in. (51mm) +T s

D*

TYPE R

16 in. (406mm)

Min.

2

1

/

8

in.

D* + 2 in. (51mm)+T

s

TYPE O

W

*

H*

W*

+ 2 in. (51mm)+Ts

H* + 2 in. (51mm)+Ts

W*

H*

TYPE C

H* + 2 in. (51mm)+Ts

(54mm)

16 in. (406mm)

Min.

2

1

/

8

in.

(54mm)

16 in. (406mm)

Min.

W*+ 2 in. (51mm)+Ts

(54mm)

2

1

/

8

in.

Copyright ©

2007 Greenheck Fan Corporation

SMD-401M Rev. 5 April 2007