Greenheck Fan DH100ACDCLP User Manual

Duct smoke detector, Dh100acdclp

Advertising
background image

Purpose/Application

National and local safety standards and codes recognize
the ability of air duct systems to transfer smoke, toxic
gases, and flame from area to area. Sometimes smoke can
be of such quantity as to be a serious hazard to life safety
unless blowers are shut down and dampers are actuated.
The primary purpose of duct smoke detection is to prevent
injury, panic, and property damage by reducing the spread
(recirculation) of smoke. The detector samples air currents
passing through a duct and gives dependable performance
for management of smoke and combination fire smoke
dampers. Duct smoke detection can also serve to protect the
air conditioning system itself from fire and smoke damage.

There are several important documents that provide guidance
concerning the performance, application and installation of
duct detectors:

1) NFPA Standard 90A, Installation of Air Conditioning

and Ventilating Systems

2) NFPA Standard 92A, Recommended Practice for

Smoke Control Systems

3) NFPA Standard 72, National Fire Alarm Code
4) NFPA Standard 101, Life Safety Code
5) UL Standard 268A, Standard for Smoke Detectors for

Duct Applications

6) ASHRAE Handbook and Product Directory, “Fire and

Smoke Control”

7) System Sensor, Guide for Proper Use of Smoke

Detectors in Duct Applications

.

Duct detectors are:

NOT a substitute for an open area smoke detector.
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection
system.

Availability

For use with all FSD, SSFSD, SMD, SSSMD, and CFSD
models. Not available on SMDR models.

Listings

UL 268A

Configuration

Maximum wall thickness: 6 in. (152mm) on FSD & SSFSD

applications

(Consult factory for walls greater
than 6 in. [152mm])

Actuator Location: Must be right hand drive

Must be externally mounted

Detector Location: Mounts opposite actuator side

Must be external

Sampling tubes longer than three feet must be supported
on each end. Holes in duct smoke detector sampling tubes
must face into the airflow.

Specifications

Type: Photoelectric

Air duct velocity: 100 to 4000 fpm (.5 m/s to

20.3 m/s)

Operating temperature range: 32°F to 131°F (0°C to 55°C)

Operating humidity range: 10% to 93% R.H.

Operation Voltage: 24 VAC/DC or

120/240 VAC

Features

• Textured cover for convenient visual inspection.
• The detector provides a trouble signal in the event that the

front cover is removed.

• Integral filter system included to reduce dust and residue

effects on detector and housing, thereby reducing
maintenance and servicing.

• Terminal connections are of the strip and clamp method

suitable for 12-18 AWG wiring.

• Outside mounting tabs for easy connection to sleeve or

ductwork (when detector ships loose).

DUCT SMOKE DETECTOR

DH100ACDCLP

Refer to Greenheck Installation Supplement: Part #463813 IOM-Smoke Detector Supplement