Warranty, Troubleshooting, Cwb belt drive centrifugal sidewall exhaust fan – Greenheck Fan Centrifugal Sidewall Exhaust Fans CW/CWB User Manual

Page 8

Advertising
background image

8

457691 • Models CW/CWB, Rev. 5, September 2008

Copyright 2008 © Greenheck Fan Corp

Greenheck warrants this equipment to be free from defects in material and workmanship for a period of
one year from the purchase date. Any units or parts which prove defective during the warranty period will
be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the
motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during
this period, they should be returned to the nearest authorized motor service station. Greenheck will not be
responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.

Greenheck Catalog Series C provides additional information describing the

equipment, fan performance, available accessories, and specification data.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Warranty

AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial

and Commercial Fans, provides additional safety information. This publication

can be obtained from AMCA International, Inc. at: www.amca.org.

Troubleshooting

WARNING: Before taking any corrective action, make certain unit is not capable of operation during repairs.

PROBLEM

CAUSE

CORRECTIVE ACTION

Excessive Noise

or Vibration

Bad Bearings

Replace.

Wheel unbalance

Clean and remove all dirt buildup off wheel. Check wheel
balance, rebalance in place if necessary.

Belts too tight or too loose

Adjust tension, see figure 12a-b.

Wheel improperly aligned and
rubbing

Center wheel on inlet, see figure 7.

Loose drive or motor pulleys

Align and tighten. See “Pre-Starting Checks”, see page 4-6.

Foreign objects in wheel or
housing

Remove objects, check for damage or unbalance.

Reduced airflow

System resistance too high

Check system: Proper operation of backdraft or control
dampers, obstruction in ductwork, clean dirty filters.

Unit running backwards

Correct as shown in figure 8.

Excessive dirt buildup on wheels

Clean wheel.

Improper wheel alignment

Center wheel on inlets, see Pre-Starting checks and figure 7.

CWB Belt Drive Centrifugal Sidewall Exhaust Fan

Mounting Plate

Windband

Birdscreen

Breather Tube

Motor Compartment

Wheel

Cover