Installation Instructions

EXHAUST BLOWER SAFETY WARNING

Sufficient air is needed for proper combustion and exhausting of gases through the flue
(chimney) of other fuel burning equipment to prevent back drafting. Follow the heating
equipment manufacturer’s guidelines and safety standards such as those published by
the National Fire Protection Association (NFPA), the American Society for Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE) and local code authorities.

NOTE: The exhaust blower output is approximately 400 CFM (cubic feet per minute)
without ductwork. Each installation is different and ductwork affects blower output
accordingly. Actual blower exhaust CFM can be approximated using the graph below.

Step 1: Calculate the “equivalent duct length” using the “DUCTWORK

CALCULATIONS” table in these instructions for your installation.

Step 2: Find the approximate intersection point of the blower exhaust performance

curve with the equivalent duct length to estimate the actual maximum blower
output for your installation.

Examples: 50 equivalent feet of ductwork has approximately 320 CFM.

100 equivalent feet of ductwork has approximately 265 CFM.

Downdraft Cooktop Exhaust Blower CFM

Air Flow (CFM)

6” Diameter Equivalent Duct Length

450

400

350

300

250

200

150

100

50

0

0

25

50

75

100

125

150

EXHAUST BLOWER RATINGS