Filtered supply wall housing mounting options, Closure angles – Greenheck Fan SE1 User Manual

Page 10

Advertising
background image

10

Filtered supply wall housings are available in seven sizes
for fans ranging from size 24 to 54 inches (610 to 1372 mm).
They are designed with the draw-thru concept to achieve the
highest filter and fan efficiencies.

Standard construction is galvanized steel (painted steel
optional). Mounting flanges are factory installed for either flush
exterior or flush interior. Permanent 2 inch (51 mm) washable
filters are accessed through a bolted panel and can be easily
removed for cleaning.

All accessory items available with the standard wall housing can be used with the filtered supply wall housing.

Size

A

B

C

Wall Opening

Filter Size & Quantity

24

32

1

4

(819)

63 (1600)

24 (610)

33

3

4

(857)

(4) 23

1

4

(591) x 16

1

4

(413)

30

38

1

4

(972)

65 (1651)

26 (660)

39

3

4

(1010)

(4) 24

5

8

(625) x 19

1

4

(489)

36

44

1

4

(1124)

67

1

4

(1708)

28

1

4

(718)

45

3

4

(1162)

(6) 23

1

4

(591) x 22

1

8

(562)

42

50

1

8

(1273)

72

7

8

(1851)

34 (864)

51

3

4

(1314)

(6) 24

1

8

(613) x 25

1

8

(638)

48

56

1

8

(1426)

72

7

8

(1851)

34 (864)

57

3

4

(1467)

(12) 23

1

4

(591) x 18

3

4

(476)

54

62

3

8

(1584)

79

11

16

(2024) 40

11

16

(1033)

63

3

4

(1619)

(12) 23

1

4

(591) x 20

3

4

(527)

Filters are 2 in (51 mm) nominal thickness. Above filter sizes are actual dimensions. All dimensions given in
inches (mm)
.

Wa

ll

INTERIOR

EXTERIOR

Closure Angles

Mounting
Angles

Diffusers - Wall Housing Mounted - Manual Operator

Diffusers are constructed with heavy gauge galvanized steel frames,
blades and prepunched mounting flanges. They are designed to mount to
the interior end of the wall housing when used in the supply configuration.
Manual quadrants set the angle of the blades to deflect air in 1, 2 or 4
directions.

Closure Angles

An extra set of mounting flanges is available for field installation to close
off the interior wall opening for a finished appearance.

Notes:

1. Additional bracing (by others) above or below the

housing is required for support of the filtered supply
wall housing.

Attach at least two supports (either vertical or angled)
to the end of housing.

Vertical supports must carry 500# minimum per
support, and angled (45°) supports a minimum of 750#
per support.

2. Filtered supply wall housing, fan damper and guards

ship completely factory assembled. Weatherhood
ships loose.

Filtered Supply Wall Housing
Mounting Options

Weatherhood

Weatherhoods shield wall openings and dampers from rain and snow. Weatherhoods are
shipped unassembled in kit form for field assembly. Construction is of galvanized steel with
wire mesh birdscreen. Mounting flanges have prepunched mounting holes. 45° turn down is for
exhaust and 90° turn down is for exhaust and supply. Options include aluminum construction,
insect screen and painted finish.

Damper Guard

Damper guards meet the OSHA requirements completely enclose the damper or wall openings
on the discharge side of the fan. They are constructed of expanded galvanized steel screen in
galvanized steel frames. Mounting flanges have prepunched mounting holes. Options include
aluminum construction and painted finish.

Dampers

Used alone or in conjunction with the wall housing or wall collar, a complete line of dampers is
available for exhaust or supply configurations

FILTERED SUPPLY FAN in Wall Housing with Filter
Bank, Gravity Damper and Weatherhood

Note: This chart is for manual
calculations only. CAPS has
filter losses built into the
selection tool when the filtered
housing option is selected.