36 belt drive sbe/sbs, Model sbe for exhaust — model sbs for supply – Greenheck Fan SE1 User Manual

Page 29

Advertising
background image

29

36 Belt Drive SBE/SBS

Model SBE for exhaust — Model SBS for supply

Model Number

Motor

HP

Fan

RPM

Max

BHP

*Sones

CFM / Static Pressure in Inches WG

0.00

0.10

0.125

0.15

0.20

0.25

0.30

0.375

0.50

0.625

0.75

1.00

Level 1 Performance

Max RPM L - 551 H - 694

Max Motor Frame Size - 56

TS = RPM x 7.854

SBE/SBS-1L36-3

1/3

329

0.25

12.3

9491

6448

361

0.34

11.8

10415 7958

6849

384

0.40

11.8

11078

8915

8018

6662

SBE/SBS-1H36-3

1/3

410

0.25

10.0

9011

6831

6112

450

0.33

11.1

9890

7967

7391

6725

481

0.40

12.1

10572

8812

8290

7743

SBE/SBS-1L36-5

1/2

412

0.50

12.7

11886 9913

9250

8354

438

0.61

13.6

12636 10809 10290 9572

SBE/SBS-1H36-5

1/2

521

0.52

13.5

11451 9845

9398

8912

7811

556

0.61

14.9

12220 10729

10328 9891

8958

SBE/SBS-1L36-7

3/4

471

0.76

14.5

13588 11925 11442 10947 9408

500

0.90

15.3

14425 12890 12435 11981 10808 8915

SBE/SBS-1H36-7

3/4

591

0.75

16.4

12989 11605 11223

10844 9985

9016

628

0.90

18.2

13802 12520 12156 11800

11035 10205

9228

SBE/SBS-1L36-10

1

518

1.01

16.1

14944 13482 13044 12605 11569 10084

551

1.21

17.7

15896 14558 14146 13733 12908 11731 10007

SBE/SBS-1H36-10

1

651

1.01

18.8

14308 13083 12731 12386 11668 10880 9995

694

1.23

20

15253 14135 13798 13468 12824 12111 11358 9875

Level 2 Performance

Max RPM L - 693 H - 870

Max Motor Frame Size - 184T

TS = RPM x 7.854

SBE/SBS-2L36-10

1

518

1.01

16.1

14944 13482 13044 12605 11569 10084

550

1.21

17.6

15867 14525 14113 13699 12873 11682 9934

SBE/SBS-2H36-10

1

651

1.01

18.8

14308 13083 12731 12386

11668 10880 9995

694

1.23

20

15253 14135 13798 13468

12824 12111 11358 9875

SBE/SBS-2L36-15

1

1

2

593

1.51

20

17108 15909 15527 15144 14377 13512 12329

631

1.81

22

18204 17113 16759 16400 15680 14959 14025 12176

SBE/SBS-2H36-15

1

1

2

744

1.50

23

16352 15358 15021 14714 14106

13486 12810 11706

792

1.80

27

17407 16519 16198 15894 15316

14753 14145 13170

SBE/SBS-2L36-20

2

653

2.01

24

18839 17784 17467 17120 16424 15728 14942 13287

693

2.41

27

19993 18999 18744 18416 17762 17106 16450 15154

SBE/SBS-2H36-20

2

821

2.02

30

18044 17217 16907 16601 16043 15496

14935 14011 12258

870

2.40

34

19121 18388 18096 17803 17259 16736

16223 15389 13871

Level 3 Performance

Max RPM L - 819 H - 1321

Max Motor Frame Size - 184T

TS = RPM x 7.854

SBE/SBS-3L36-20

2

614

1.52

18.1

16901 15679 15294 14909 14075 13113 11866

675

2.02

20

18580 17464 17178 16828 16128 15335 14463 12727

716

2.41

22

19709 18646 18404 18098 17438 16759 15972 14576

SBE/SBS-3H36-20

2

833

1.52

26

15014 14373 14212 14041 13682

13275 12740 11908 10095

915

2.04

30

16492 15908 15762 15616 15299 14972

14598 13867 12585 10735 8063

967

2.40

33

17429 16877 16739 16600 16313 16003 15694

15059 13876 12427 10502

SBE/SBS-3L36-30

3

771

3.01

25

21223 20222 19997 19772 19169 18556 17898 16802 14296

819

3.60

28

22544 21590 21378 21166 20658 20081 19504 18511 16505

SBE/SBS-3H36-30

3

1046 3.00

38

18853 18342 18215 18087 17831 17554 17268

16833 15767 14646 13192

1106 3.60

40

19935 19452 19331 19210 18968 18721 18450 18044

17147 16121 15045 11743

SBE/SBS-3H36-50

5

1241 5.01

52

22368 21937 21830 21722 21507 21291 21076 20715 20113 19273 18372 16280

1321 6.00

59

23810 23405 23304 23203 23001 22799 22596 22277 21711 21077 20233 18473

CFM values shown
in black are the most
efficient selections.
Values shown in gray
are not recommended.

Performance certified is for Models SBE/SBS for installation type A: free inlet, free outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).

*

Speed (RPM) shown is nominal. Performance is based on actual speed of test.

The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values are for installation
type A: free inlet hemispherical sone levels.
*Sones shown apply to the highest cataloged CFM in black type at each fan RPM. For selections at other CFM and static pressure points, refer to the CAPS
computerized selection program.

Numbers in blue have a larger BHP and require the next size larger motor.