Nonincendive field wiring (control drawing #dr00) – GE Panel C GFK-2251 User Manual

Page 60

Advertising
background image


A-4

Panel C Industrial Computer Hardware User's Manual

May 2003

GFK-2251

A

Nonincendive Field Wiring (Control Drawing #DR00)

1

USB Port PL6

USB Port PL6

USB Port PL10

Ethernet Port

Keyboard Port

Mouse Port

Panel C

Associated Nonincendive
Field Wiring Apparatus

Hazardous (Classified) Location Class I,
Division 2 Groups A, B, C, and D

Non-hazardous Area

Notes:

1. Nonincendive

Circuit

Parameters:

Panel C Industrial Computer

Vmax = 5VDC

Voc = 5 VDC

Imax = 500mA

Isc = 500mA

Ci = 34.2µF

Ca = 1000µF

Li = 0mH

La = 5mH

2. Selected Associated Nonincendive Field Wiring Apparatus must satisfy the

following requirements:

Associated Nonincendive

Field Wiring Apparatus

Panel

C

Industrial Computer

Voc

Vmax

Isc

Imax

C

a

Ci + C cable

La

Ci + C cable

Vmax

Voc

Imax

Isc

Ci + Ccable

Ca

Li + Lcable

La

3. If the electrical parameters of the cable are unknown, the following values may be

used:

Capacitance – 60 pF/ft
Inductive – 0.20 µH/ft

4. Nonincendive Field Wiring must be installed in accordance with Article 501.4(B)(3)

of the National Electrical Code ANSI/NFPA 70.