2.2.10 UPS command group

The UPS command group allows monitoring and configuration of the managed UPS system.

Command Parameters

Description

upsinfo

(*)

Show detailed UPS information

upstest

(*)

Start/Stop UPS tests

upscontrol

(*)

Control the UPS (1-ph/SP versions ONLY)

upsconfig

(*)

Configure UPS parameters

attacheddevice [device]

Set UPS attached device
[device]

Device which is powered/protected by the UPS

NOTE: Maximum length 63 chars. If this parameter contain
blanks or special characters it shall be specified in between
double quotation marks (“...”)

alarmdelay

[time]

Set alarm delay time (1-ph/SP version ONLY)
[time] Time in seconds before alarm notification
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so

retrydelay

[time]

Set retry delay time (1-ph/SP version ONLY)
[time] Time in seconds between re-connection attempts
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so

retrycount

[count]

Set retry count (1-ph/SP version ONLY)
[count] Number of re-connection attempts
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so

serialbypass

on | off

Enable/disable the serialbypass functionality
NOTE: This command is offered for UPS service access ONLY.
It use outside of this scope is not recommended (enabling
this functionality stops the UPS monitoring

Show/Set card address on the IMV bus
[address]

Card address in the range 0, 54-57

NOTE: This setting may overrides the HW setting through the
dip-switches on the card. Setting this parameter to 0 reverts
to the HW settings.
This setting becomes active only after reboot (save the
settings!)

[address]

cardaddress

Enable/disable write commands to the UPS
Setting readonlymode to on will stop any write operation
towards the UPS (the SNMP/Web adapter will effectively
switch to read-only mode). The UPS Test, Control and Config
web pages will not be shown in the navigator bar.

[on | off]

readonlymode

Caution! Once enabled, this setting may not be reverted.
NOTE: 1-ph/SP versions ONLY

Modifications reserved

Page 23/58

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc

Operating Manual SNMP/Web Adapter