4.3 GE MIB OBJECTS

GE provides private MIBs, which enhance the UPS information available over SNMP interface.
These MIBs are only supported on 3-ph SNMP/Web plug-in adapter.

Two different version of the GE private MIB exist:

• GE Single MIB: to be used for monitoring of a 3-ph UPS is single unit configuration
• GE Parallel MIB: to be used for monitoring of a 3-ph parallel UPS system


The MIB structure is shown in the following picture. The geGenericUPS group provides information on
the unit in stand-alone configuration or on the overall system in a parallel configuration. The geFirstUPS
geEightUPS groups provide information on the units that are part of a parallel configuration.













For each of these groups the 3-ph SNMP/Web plug-in adapter supports the following objects.
(Objects marked with [*] do not have a RFC1628 correspondence)

OIDs

TRAPS & ALARMS

==== upsIdent Group ====

upsIdentManufacturer
upsIdentModel
upsIdentUPSSoftwareVersion
upsIdentAgentSoftwareVersion
upsIdentName

upsIdentAttachedDevices
upsIdentsUPSSerialNumber [*]
upsIdentComProtVersion [*]
upsIdentOperatingTime [*]


==== uspBattery Group ====

upsBatteryStatus
upsSecondsOnBattery
upsEstimatedMinutesRemaining

upsEstimatedChargeRemaining
upsBatteryVoltage

upsBatteryCurrent

upsBatteryTemperature
upsBatteryRipple [*]

==== upsInput Group ====
upsInputLineBads

upsInputNumLines
upsInputFrequency

==== geUPSTraps & upsWellKnownAlarms group

====
upsAlarmBatteryBad
upsAlarmOnBattery

upsAlarmLowBattery
upsAlarmDepletedBattery
upsAlarmTempBad

upsAlarmInputBad
upsAlarmOutputBad

upsAlarmOutputOverload
upsAlarmOnBypass
upsAlarmBypassBad
upsAlarmOutputOffAsRequested
upsAlarmUpsOffAsRequested

upsAlarmChargerFailed

upsAlarmUpsOutputOff
upsAlarmUpsSystemOff

upsAlarmFanFailure

geUPS (1.3.6.1.4.1.818.1.1)

geGenericUPS(10)

geFirstUPS(11)

geSecondUPS(12)

geEigthUPS(18)

Parallel
system
only

geUPS (1.3.6.1.4.1.818.1.1)

geGenericUPS(10)

geFirstUPS(11)

geSecondUPS(12)

geEigthUPS(18)

Parallel
system
only

upsAlarmFuseFailure
upsAlarmGeneralFault

upsAlarmDiagnosticTestFailed
upsAlarmCommunicationsLost

upsAlarmAwaitingPower
upsAlarmShutdownPending
upsAlarmShutdownImminent