2 CONSOLE INTERFACE



2.1 INTRODUCTION

The console interface provides a simple way to configure the SNMP/Web adapters through a
command-line interface. Actually, the console interface provides a full set of commands, extending far
beyond the adapter initial configuration and allowing access to all advanced functionalities.
Nevertheless, access using the console interface (by means of a local serial connection) is normally
needed only for initial configuration, when no DHCP server is available or the IP-address is not known.

The console interface can be accessed locally (serial connection) or remotely (Telnet, SSH).


2.1.1 Local connection

Local access requires a local computer connected to the adapter serial port using a straight serial
cable:

• Connect the SNMP adapter to a computer using a standard 1:1 serial communication cable.
• Run a terminal simulator (e.g. HyperTerminal on a PC running Windows)
• Configure the terminal simulator as follows:

115,200bps, 8 data bits,

1 stop bit,

parity none,

flow control none

terminal emulation VT-100

• Establish the connection and press <enter>
• The default username (login) and password are ge and ge
• A command-line configuration interface is entered