(*) By running these commands, an interactive menu is launched – follow the on-screen instructions.
The menu also provide a complete on-line help section.

NOTE: When using the local serial connection, make sure that the terminal emulation is set to VT-100,
otherwise the interactive menu may not be rendered correctly.

Caution! Some of these commands (particularly upscontrol and upsconfig) may inject commands
and/or alter the UPS configuration with consequences on the UPS operation that may affect the load.
Make sure you fully understand the effect on the UPS and on the load before injecting any of these
commands. Make sure that it is safe to perform the desired operation for both the UPS and the load.




2.2.11 Rccmd command group

The rccmd command group allows to configure the RCCMD Server embedded in the SNMP/Web
adapter.

Command Sub-command Parameters

Description

showrccmd

Shows the current RCCMD Server
configuration

Enable/disable Network Shutdown function

on|off

on

Network Shutdown enabled

off

Network Shutdown disabled)

add

Add an RCCMD Client
[ip]

IP-address of the trap target

[port] Port on which the client is listening
[cond] Shutdown condition:

aXX

after XX minutes on battery

bXX

at XX min remain batt time

[ip]
[port]
[cond]

rccmd

Send an RCCMD test message to a specific
RCCMD client

[num]

test

[row] RCCMD client reference

Delete an RCCMD Client
[row] RCCMD client reference

[num]

del




Modifications reserved