3.3.2 Battery page

The Battery page shows the following information.

Parameter Name

Description

The current status of the battery:

1 – unknown

Battery Status

2 – normal The remaining run-time on batteries is greater than

the UPS low battery time (ref. UPS Config page)

3 – low

The remaining run-time is less than or equal the UPS low

battery time (ref. UPS Config page)

4 – depleted The battery would be unable to sustain the load, if mains

power is lost

Seconds On Battery

The time elapsed since the UPS switched to battery power (in seconds)

Estimated Minutes Remaining

An estimate of the remaining run-time on batteries, under present load

conditions (in minutes)

An estimate of the remaining battery charge (in percentage – 100% is full

charge)

Estimated Charge Remaining

The present battery voltage (in Volts)

Battery Voltage

The battery flowing from/to the battery (in Amperes)

Battery Current

The ambient temperature of the UPS batteries (in °C)

Battery Temperature

The RSM ripple on the DC link (in Vrms)

Battery Ripple