Installation instructions, Site requirements – Stovax Huntingdon 30 User Manual

Page 9

Advertising
background image

9

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1.1

The chimney or flue system must comply with the rules in

force, and must be a minimum of 127mm in diameter. (5").

1.2

The minimum flue height for the appliance must be 3

metres (10ft). Any horizontal flue run from the rear outlet

must not exceed 100mm from the back of the appliance.

1.3

The chimney or flue must be free from any obstruction. Any

damper plates must be removed or secured in the fully

open position, and no restrictor plates fitted.

1.4

The chimney must be swept prior to the installation, but it

need not be swept if it can be seen the chimney is clean

and unobstructed throughout its entire length.

1.5

A5" (127mm) liner must be used if fitting the stove into an

existing brick built chimney.
Larger lined flues can work, but in some instances could

cause cold start flue problems resulting in nuisance

shutdown. Lined flues above 7" (175mm) are not

recommended.

1.6

Due to recent changes to European chimney standards,

new flues and chimneys are described by their temperature,

pressure and resistance to corrosion, condensation and fire.

To assist in identifying the correct flue system, the minimum

flue specification is shown in the Technical Specification.

Existing chimneys are not covered by this system.

2.1

Consult the rules in force.
Note: This appliance does not normally require any

additional ventilation when installed in G.B.

3.1

Before installation, ensure that the local distribution

conditions (identification of the type of gas and pressure)

and the adjustment of the appliance are compatible.

3.2

Ensure the gas supply is capable of delivering the required

amount of gas, and is in accordance with the rules in force.

3.3

Soft copper tubing and soft soldered joints can be used but

must not be closer than 50mm to the base of the tray.

3.4

A means of isolating the gas supply to the appliance must

be provided independent of any appliance control.

3.5

All supply gas pipes must be purged of any debris that may

have entered, prior to connection to the appliance.

4.1

This appliance must stand on a non-combustible hearth that

is at least 12mm thick, and project a minimum of 50mm

from the base of the stove in all directions, Diagram 1.

4.2

This appliance must not be installed in a room that contains

a bath or shower.

4.3

The stove is not suitable for installation against a

combustible wall; all combustible materials must be

removed from the area behind the stove.

4.4

Ensure you comply to all minimum clearances to

combusible materials. See Diagram 2 & 2A.

In a non-combustible recess be careful to allow enough

clearance at the sides and rear of the stove to perform

spillage tests and reach the controls

.

2A

AR0531

2

AR0522

150

225

853

150

1

A = 653
B = 501
C = 12

AR0604

4. APPLIANCE LOCATION

3. INSTALLATION OF THE GAS SUPPLY

2. VENTILATION

1. FLUE AND CHIMNEY REQUIREMENTS

Advertising