Sequence of operation – GE ZBTSD User Manual

Page 26

Advertising
background image

24

GE Zenith Controls

ZBTS / ZBTSD Operation and Maintenance Manual (71R-4000A)

1600-4000 AMP

1) Automatic

a) Manually operated Bypass Switch contacts

(BN/BE) are open and ATS is supplying load.

b) Disconnect Switch (DS) is in Auto.

2) To Bypass ATS

a) Open bottom cabinet door and turn DS to Inhibit.
b) Turn Bypass Selector Switch (BSS) to same power

source as ATS

c) Position manual bypass handle (MBH) upward.

3) To Test ATS

a) Bypass per above instructions.
b) Rotate crank mechanism counter-clockwise until

ATS test light is illuminated.

c) Turn DS to Auto.
d) Test Switch (TS) on bottom cabinet door will allow

electrical operation of ATS.

4) To Isolate ATS

a) Bypass per above instructions.
b) Rotate crank mechanism counter-clockwise

until ATS Isolated light is illuminated.

5) To Remove ATS

a) Bypass and isolate per above instructions.
b) Disconnect multipin plugs and external

connections to ATS.

c) Slide four corner latches of ATS to innermost

position.

d) ATS can now be removed from cabinet.

6) To Reconnect ATS

a) Roll cart back into cabinet.
b) Slide four corner latches of ATS to outermost

position.

c) Turn DS to Inhibit.
d) Manually position ATS into same source

as Bypass Switch.

e) Reconnect multipin plugs and external

connections to ATS.

f) Rotate crank mechanism clockwise until

ATS Test light is illuminated.

g) Turn DS to Auto and use TS to electrically

operate ATS.

h) Turn DS to Inhibit.
i) Rotate crank mechanism clockwise until ATS

location pointer is aligned with Auto mark
on location indicator. (ATS must be in same
source as Bypass.)

j) Turn DS to Auto and open Bypass with MBH.
k) ATS is now fully automatic.

Notes:
1. DS in Inhibit will prevent ATS electrical operation.
2. DO NOT use excessive force on mechanical handles.
3. Figures depict Bypass Source 1. Sequence is the same for Bypass Source 2.
4. When ATS is in Test or Isolate, Bypass Switch is a manual transfer switch to either available source (indicated on light panel).
5. To operate Bypass Switch when ATS is in Test or Isolate:

a) Move MBH downward (to open Bypass Contacts BN/BE)
b) Turn BSS to opposite power source.
c) Move MBH upward to close into selected power source.

Legend:
1. BP - Bypass switch (indicated by contacts BN/BE) is a three position switch.
2. ATS - Automatic Transfer Switch.

Sequence of Operation