Controls power supply (cps), Standard and delay transition – GE ZBTSD User Manual

Page 27

Advertising
background image

GE Zenith Controls

25

ZBTS / ZBTSD Operation and Maintenance Manual (71R-4000A)

Standard and Delay Transition

Each Entelli-Switch 250 microprocessor based ATS
controller requires Controls Power Supply (CPS) to apply
line voltage to the ATS operator via SCRs. Also required is
power for the Entelli-Switch 250 printed circuit board and
an application of sensing voltage proportional to line

voltage. This is accomplished by the Controls Power Supply
(CPS). This method of switching operator voltage and
applying power and sensing voltage to the printed circuit
board isolates the MX250 from the line voltage, further
protecting the controller from harmful line transients.

Controls Power Supply (CPS)

Primary

CPS

CPS

Voltage

Assembly

Board

at 50/60 Hz

Part No.

No.

120V

50P-1224

50P-1200

208-220V

50P-1225

50P-1201

230-240V

50P-1226

50P-1202

277V

50P-1227

50P-1203

380-400V

50P-1228

50P-1204

416-440V

50P-1229

50P-1205

460-480V

50P-1230

50P-1206

575-600V

50P-1231

50P-1207

Advertising