Page header, Volume total pressure – Greenheck Fan AX User Manual

Page 36

Advertising
background image

Page Header

36

Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.

88

87

90

88

86

88

85

83

90

Pitch Angle º

rpm

5

10

15

20

25

30

35

1770 (Bhp/kW)

4.98/3.72 6.43/4.80 8.55/6.38 11.2/8.36 14.4/10.7 17.9/13.4 21.9/16.3

1170 (Bhp/kW)

1.44/1.07 1.86/1.39 2.47/1.84 3.24/2.42 4.14/3.09 5.18/3.86 6.32/4.71

1450 (kW)

2.04

2.64

3.51

4.60

5.88

7.35

8.97

950 (kW)

0.57

0.74

0.99

1.29

1.65

2.07

2.52

Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]

Sound Power A-Weighted [LwA]
Sound Pressure [dBA]

Inlet Sound

rpm

LwA

dBA

1770

+11

-0.5

1170

-

-11.5

1450

+6

-5.5

950

-5

-16.5

Volume

Total

Pressure

Impeller Diameter = 32.38 inches (822 mm)

Outlet Velocity

ft/min = cfm / 5.72
m/s = m³/s / 0.53

Tip Speed

ft/min = rpm X 8.48
m/s = rpm X 2.58

Air density = 1.2 kg/m³
Air density = 0.075 lbs/ft³

36

AX 80-400 6 Blades

Advertising