Page header, Volume total pressure – Greenheck Fan AX User Manual

Page 58

Advertising
background image

Page Header

58

Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.

100

100

99

99

98

97

94

92

100

Pitch Angle º

rpm

5

10

15

20

25

30

35

1170 (Bhp/kW)

11.4/8.53 18.0/13.4 26.2/19.5 35.9/26.8 47.3/35.3 60.2/44.9 74.6/55.7

870 (Bhp/kW)

4.70/3.51 7.40/5.52 10.8/8.02 14.8/11.0 19.4/14.5 24.7/18.5 30.7/22.9

1450 (kW)

16.2

25.6

37.2

51.0

67.1

85.5

106

950 (kW)

4.57

7.19

10.5

14.4

18.9

24.0

29.8

Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]

Inlet Sound

rpm

LwA

dBA

1170

+8

-3.5

870

-

-11.5

1450

+14

+2.5

950

+3

-8.5

Volume

Total

Pressure

Impeller Diameter = 55.0 inches (1400 mm)

Outlet Velocity

ft/min = cfm / 16.50
m/s = m³/s / 1.53

Tip Speed

ft/min = rpm X 14.4
m/s = rpm X 4.39

Sound Power A-Weighted [LwA]
Sound Pressure [dBA]

Air density = 1.2 kg/m³
Air density = 0.075 lbs/ft³

58

AX 140-533 8 Blades