Application data, Damper sleeve dimensional data, Actuators and accessories space envelopes – Greenheck Fan Steel Airfoil Blades FSD-331 User Manual

Page 6

Advertising
background image

5

3

/

8

"

5"

Right hand drive is shown

Left hand drive available upon request

LH

RH

A

Sleeve Length

Varies

6"

3

3

/

4

"

11/2" max.

B*

S

T*

damper sleeve dimensional data

The drawings below and corresponding table show the position of the FSD-331 damper when mounted in a factory sleeve.

The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for

installation of retaining angles and duct connections.

The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be

positioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.

Actuators and Accessories

space envelopes

Externally mounted actuators always require space

outside of the damper sleeve. The “S” dimension

illustrates the clearance required for various available

actuators.

On dampers less than 18 in. (457mm) high, actuators

may also require clearances above and/or below

the sleeve. “B” and “T” dimensions are worst case

clearance requirements for some dampers less

than 18 in. (457 mm) high. All damper sizes under

18 in. (457mm) high do not require these worst case

clearances. If space availability above or below the

damper sleeve is limited, each damper size should be

individually evaluated.

Application data

5

3

/

8

"

5"

Right hand drive is shown

Left hand drive available upon request

LH

RH

A

Sleeve Length

Varies

6"

3

3

/

4

"

11/2" max.

B*

S

T*

*With the exception of dampers 10 in. high (254mm) or less.

NOTE: Entire damper frame is not required to be installed within the

wall. The damper blades, when closed should be contained within

the wall.

in. (mm)

"A" Dimension

Standard

Maximum

All Dampers*

7 3/16 (183)

12 (305)

When H is 11 in. (279mm) or
less with OCI, RRL, or TOR

12 (305)

12 (305)

* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .

Actuator Type/Model

B*

T*

S

With

RRL, RRL/OCI, or TOR

With

RRL, RRL/OCI, or TOR

120 Volt AC

ML-4XXX Series Honeywell

5¼ in. (133mm)

¾ in.(19mm)

6 in. (152mm)

MS-4XXX Series Honeywell

6 in. (152mm)

3/8 in. (10mm)

6 in. (152mm)

MS-4120 Series Honeywell

6 in. (152mm)

3/8 in. (10mm)

6 in. (152mm)

24 Volt AC

ML-8XXX Series Honeywell

5¼ in. (133mm)

¾ in.(19mm)

6 in. (152mm)

MS-8XXX Series Honeywell

6 in. (152mm)

6 in. (152mm)

6 in. (152mm)

MS-8120 Series Honeywell

6 in. (152mm)

6 in. (152mm)

6 in. (152mm)

Pneumatic (25 psi min.)

331-4551 Powers

1 in. (25mm)

6¼ in. (159mm)

6½ in. (165mm)

331-2976 Powers

2 3/8 in. (60mm)

12 1/8 in. (308mm)

9¼ in. (235mm)

MK2-7121 Invensys

3 3/4 in. (95mm)

16½ in. (419mm)

10 in. (254mm)

Advertising